Plan Review Notes
Plan Review Notes For Permit 06050037
Permit Number 06050037
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-02 00:00:00DENIED
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE
 BUILDING ON THE APPLICATION.
  
 2) CIRCLE THE FASTENING OPTION THAT YOU
 WILL USE ON SHEET 17 OF THE NOA FOR THE
 MODIFIED SYSTEM.
  
 3) THE PRESSURES LISTED FOR THE MODIFIED
 SYSTEM. WILL NOT MEET THE REQUIRED
 COMPONENT AND CLADDING WIND LOADS LISTED
 IN FBC TABLE 1609.6B. THEREFORE,
 ENHANCED FASTENING IS REQUIRED, SEE
 LIMITATION #7. LIMITATION #7 ON SHEET 20
 OF THE NOA REQUIRES THE CALCULATIONS FOR
 FASTENER DENSITIES TO BE DONE BY AN
 ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT. SUBMIT RAS 117 CALCULATIONS
 SIGNED AND SEALED BY AN ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714