Plan Review Notes For Permit 06050037 |
Permit Number |
06050037 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-02 00:00:00 | DENIED | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE | | BUILDING ON THE APPLICATION. | | | | 2) CIRCLE THE FASTENING OPTION THAT YOU | | WILL USE ON SHEET 17 OF THE NOA FOR THE | | MODIFIED SYSTEM. | | | | 3) THE PRESSURES LISTED FOR THE MODIFIED | | SYSTEM. WILL NOT MEET THE REQUIRED | | COMPONENT AND CLADDING WIND LOADS LISTED | | IN FBC TABLE 1609.6B. THEREFORE, | | ENHANCED FASTENING IS REQUIRED, SEE | | LIMITATION #7. LIMITATION #7 ON SHEET 20 | | OF THE NOA REQUIRES THE CALCULATIONS FOR | | FASTENER DENSITIES TO BE DONE BY AN | | ENGINEER, ARCHITECT OR REGISTERED ROOF | | CONSULTANT. SUBMIT RAS 117 CALCULATIONS | | SIGNED AND SEALED BY AN ENGINEER, | | ARCHITECT OR REGISTERED ROOF CONSULTANT. | | | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|