Plan Review Notes
Plan Review Notes For Permit 06050004
Permit Number 06050004
Review Stop B
Sequence Number 3
Notes
Date Text
2006-07-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LISTS:
  
 _XX_4.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU MAY SHOW ANCHOR SPACING BY
 CIRCLING IT ON THE APPROPRIATE CHARTS ON
 THE PRODUCT APPROVAL.PLEASE USE INK
 RATHER THAN HIGHLIGHTER.
  
 2ND REVIEW - SPECIFY ANCHORING.YOU
 HAVE CIRCLED THE CHART; THIS DOES NOT
 SHOW CODE COMPLIANCE, ANCHOR SPACING
 REQUIRED FOR PERMITTING.
  
 3RD REVIEW - THE INSTALLATION SCHEDULE
 WHICH YOU HAVE USED IS NONCOMPLIANT.IT
 REFERS TO ASCE7-98 WIND LOAD (PSF).YOU
 HAVE PUT "140" IN THAT COLUMN.THIS IS
 THE WIND SPEED, NOT THE WIND LOAD.THE
 CORRECT REFERENCE IS ASCE7-02, FBC35.
  
 YOU HAVE INDICATED THAT THERE IS A 1/3
 ALLOWABLE STRESS INCREASE.THIS IS NOT
 ALLOWED, FBC 1605.3.1.1(2).
  
 THE ANCHORING SPECIFIED, 9", IS NOT
 COMPLIANT FOR THE SPAN IN MASONRY
 SUBSTRATE.
  