Plan Review Notes For Permit 06041267 |
Permit Number |
06041267 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-05 00:00:00 | DENIED; | | 1.PAGE 8.2 ELEVATION #5 BREAK SINK TO | | COMPLY WITH FBC-2004 CHAPTER 11 SEC. | | 11-4.23.3 KNEE CLEARANCE, 27"HIGH 30" | | WIDE AND 19" DEEP FOR FRONTAL APPROACH. | | 11-4.24.6 RAP EXPOSED PIPES, 11-4.23.7 | | LEVER OPERATED FAUCET REQUIRED. (SHOW | | DETAIL). | | 2.SANITARY AND WATER ISOMETRIC DIAGRAMS | | SHOW P-9 SINKS IN ROOMS 104, 105, 107, | | AND 108. FLAT DRAWING SHOWS P-2. | | DISCRIPTION OF P-9 REQUIRED ON DRAWINGS. | | 3.SHOW TOTAL OCCUPENCY FOR COMPLIANCE TO | | FBC-2004 PLUMBING TABLE 403.1(2B). | | 4.A DRINKING FOUNTAIN IS REQUIRED. SHALL | | COMPLY WITH SECTION 410 AND | | ACCESSIBILITY CODE SEC. 11-4.1.3(10). | | SHOW DETAIL ON DRAWING. | | 5.A WASTE AND VENT BRANCH IS REQUIRED | | FOR VACUUM EQUIPMENT SEC. 713.7. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 | | |
|