Plan Review Notes
Plan Review Notes For Permit 06041240
Permit Number 06041240
Review Stop M
Sequence Number 1
Notes
Date Text
2006-05-02 00:00:00*** DENIED ***
 1) A 12"X12" SUPPLY AIR DUCT IS TO SMALL
 FOR A 5 TON A/C SYSTEM, PLEASE CORRECT.
  
 2) PLEASE SHOW ON MECHANICAL PLANS ALL
 DUCTS WITH SIZES, ALL GRILLS WITH SIZES
 AND CFM'S. AT EACH GRILL.
  
 3) PLEASE SHOW HOW RETURN AIR IS GETTING
 BACK TO AIR HANDLER.
  
 4) PLEASE ADJUST THE VALUE ON PERMIT
 APPLICATION TO SHOW VALUE OF ALL
 EQUIPMENT, MATERIALS, AND LABOR (EVEN IF
 SUPPLIED BY OTHERS) OR THE CITY WILL
 NEED TO AJUST THE VALUE.
  
 5)NEED TO FILE A NOTICE OF COMMENCEMENT,
 PER F. S. 713.13 .
  
 6) PLEASE UPDATE INSURANCE INFORMATION
 WITH THE CITY OF WPB .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.