2006-05-02 00:00:00 | *** DENIED *** | | 1) A 12"X12" SUPPLY AIR DUCT IS TO SMALL | | FOR A 5 TON A/C SYSTEM, PLEASE CORRECT. | | | | 2) PLEASE SHOW ON MECHANICAL PLANS ALL | | DUCTS WITH SIZES, ALL GRILLS WITH SIZES | | AND CFM'S. AT EACH GRILL. | | | | 3) PLEASE SHOW HOW RETURN AIR IS GETTING | | BACK TO AIR HANDLER. | | | | 4) PLEASE ADJUST THE VALUE ON PERMIT | | APPLICATION TO SHOW VALUE OF ALL | | EQUIPMENT, MATERIALS, AND LABOR (EVEN IF | | SUPPLIED BY OTHERS) OR THE CITY WILL | | NEED TO AJUST THE VALUE. | | | | 5)NEED TO FILE A NOTICE OF COMMENCEMENT, | | PER F. S. 713.13 . | | | | 6) PLEASE UPDATE INSURANCE INFORMATION | | WITH THE CITY OF WPB . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|