Plan Review Notes
Plan Review Notes For Permit 06041193
Permit Number 06041193
Review Stop M
Sequence Number 2
Notes
Date Text
2006-10-16 11:07:52PLEASE SUBMIT MECHANICAL PLANS AS A REVISION TO PERMIT
 04031591
  
 PLANS SUBMITTED APPEAR TO BE REVISIONS FOR THE
 MECHANICAL (HVAC) TO THE BUILDING & HAS NOTHING TO DO
 WITH THE GENERATOR PERTAINING TO MECHANICAL OR FUEL FOR
 THE GENERATOR.ALL VENTING TO THE DIESEL GENERATOR &
 THE GENERATOR ROOM SHALL BE SUBMITTED AS A REVISION TO
 PERMIT 04031591, AS THESE PLANS REFLECT THE ORIGINAL
 DESIGN.
  
 1.SUBMITTAL DATA FOR THE GENERATOR INDICATES SUB-BASE
 FUEL TANKWITH NO DAY TANK.THERE WILL BE NO FILL
 PIPING.
  
 2.PLEASE SUBMIT REVISIONS TO MUFFLER EXHAUST OR
 VENTILATION TO THE GENERATOR ROOM UNDER THE BUILDING
 PERMIT IN WHICH IT WAS ORIGINALLY REVIEWED.PLEASE
 NOTE, PLAN SHEET M2.01 INDICATES EXHAUST FROM THE
 GENERATOR ROOM IS TERMINATING INTO THE MAIN SWITCH GEAR
 ROOM.PER 2004 FMC 501.2, AIR REMOVED FROM EVERY
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS.502.1.3,
 EQUIPMENT ROOMMS THAT HOUSE SOURCES OFR NOXIOUS FUMES
 OR GASES, SHALL BE DESIGNED TO PREVENT SPREADING OF
 SUCH CONTAMINANTS TO OTHER OCCUPIED PARTS OF THE
 BUILDING.
  
  
 ************REVIEW IN PROGRESS