2006-09-15 00:00:00**** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE THAT THE PROPOSED
 250 GAL SUB BASE FUEL TANK DOES NOT MEET
 THE MIN REQUIRED FOR 8HRS OF OPERATION
 REQUIRED FOR FIRE PUMP AND ALL OTHER
 REQUIRED SYSTEMS FOR THEIR LOADS AT
 100%.
 PLEASE SEE NFPA-20 6.2.2
 THE FUEL SUPPLY CAPACITY SHALL BE
 SUFFICIENT TO PROVIDE 8 HOURS OF FIRE
 PUMP OPERATION AT 100 PERCENT OF THE
 RATED PUMP CAPACITY IN ADDITION TO THE
 SUPPLY REQUIRED FOR OTHER DEMANDS.
  
 2) NOTE: PLEASE SEE THAT THIS IS A
 "THRESHOLD" PROJECT AND THREE SETS OF
 PLANS AND ALL SUBMITTIALS ARE REQUIRED
 FOR REVIEW AND STAMPING. 2001 FBC
 104.2.1, 104.2.1.2 ADIMINISTRATIVE
 SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 ** PLEASE SEE THIS WAS NOTED ON PREVIOUS
 REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]