2006-09-19 00:00:00 | PERMIT: 06041193 | | ADD: 410 EVERNIA ST | | CONT: MEISNER ELECTRIC | | TEL: (561)278-8362 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | |
|