Plan Review Notes
Plan Review Notes For Permit 06041193
Permit Number 06041193
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-22 00:00:00***DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
 2) PLEASE PROVIDE PLANS INDICATING
 LOCATIONS AND DISTANCES OF GENERATOR
 EXHAUSTING TO BUILDING OPENINGS AND
 MEANS OF EGRESS.
  
 3) MORE DETAILS REQUIRED FOR FUEL TANK.
 SUBMITTAL PACKET INDICATES SUB-BASE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722