2006-06-22 00:00:00 | ***DENIED*** | | | | 1) WORK SHALL COMPLY WITH NFPA 110, | | STANDARD FOR EMERGENCY AND STANDBY POWER | | SYSTEMS. | | | | 2) PLEASE PROVIDE PLANS INDICATING | | LOCATIONS AND DISTANCES OF GENERATOR | | EXHAUSTING TO BUILDING OPENINGS AND | | MEANS OF EGRESS. | | | | 3) MORE DETAILS REQUIRED FOR FUEL TANK. | | SUBMITTAL PACKET INDICATES SUB-BASE. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|