2006-06-02 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE SPECS INDICATE 510KW
 GEN AND PLANS INDICATE 500KW?? PLEASE
 CORRELATE AND CLARIFY.
  
 2) NOTE: PLEASE BE SURE THE ENGINEER OF
 RECORD SIGNS PLANS AS ON RECORD WITH THE
 CITY OF WEST PALM BEACH.
  
 3) NOTE: PLEASE PROVIDE INFORMATION FOR
 FUEL CONSUMTION OF GEN AND MIN FUEL
 SUPPLY FOR 8HRS OF 100% LOAD OF FIRE
 PUMP AND OTHER ASSOCIATED EM LOADS AT
 100% .
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  