2006-05-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06041193
 ADD: 410 EVERNIA ST
 CONT: MEISNER ELECTRIC
 TEL: (561)278-8362
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2)PROVIDE PLANS ENOUGH TO VERIFY
 LOCATION OF GENERATOR VERSES BUILDING
 OPENINGS WINDOWS, DOORS OR SOFFIT TYPE
 VENTS, ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS.
 HORIZONTAL TERMINATIONS SHALL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.THE VENT SYSTEM SHALL TERMINATE
 AT LEAST 4 FEET (1219 MM) BELOW, 4 FEET
 (1219 MM) HORIZONTALLY FROM OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR
 GRAVITY AIR INLET INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL
 NOT BE LOCATED CLOSER THAN 3 FEET (914
 MM) TO AN INTERIOR CORNER FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE
 MOUNTED DIRECTLY ABOVE OR WITHIN 3 FEET
 (914 MM) HORIZONTALLY FROM AN OIL TANK
 VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT
 TERMINATION SHALL BE LOCATED AT LEAST 12
 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS.
 VERTICAL TERMINATIONS SHALL COMPLY WITH
 THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.WHERE THE VENT TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF
 STRUCTURE, THE TERMINATION POINT SHALL
 BE LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST
 4 FEET (1219 MM) BELOW, 4 FEET (1219 MM)
 HORIZONTALLY FROM, OR 1 FOOT (305 MM)
 ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING.
 5.A VENT CAP SHALL BE INSTALLED TO
 PREVENT RAIN FROM ENTERING THE VENT
 SYSTEM.
 6.THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM)
 HORIZONTALLY FROM ANY PORTION OF THE
 ROOF STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE.
  
 THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS AT A POINT WHERE IT WILL NOT
 CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE
 EXHAUSTED INTO AN ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL
 BE MEASURED TO THE CENTERLINE OF THE
 STREET OR PUBLIC WAY.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  