2006-06-19 00:00:00 | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)PROVIDE A FLOOR PLAN SHOWING WINDOW |
| SIZES AND LOCATIONS.SHOW ZONE 5 ON THE |
| PLAN. |
| |
| THE PRODUCT APPROVAL HAS A PRODUCT WITH |
| A DP LIMIT OF -46.1.A ZONE 5, 20SF |
| WOULD HAVE A DESIGN PRESSURE OF -46.2. |
| CONTRACTOR INDICATED THAT THE PRODUCT TO |
| BE USED WILL BE THE PRODUCT WITH +-70 |
| LIMITATION.PLEASE CIRCLE THIS ON THE |
| PRODUCT APPROVAL.+-70 IS COMPLIANT FOR |
| ALL OPENINGS REGARDLESS OF ZONE. |
| |
| 2.)INDICATE THAT THE WINDOWS ARE TO BE |
| INSTALLED IN THE SAME LOCATIONS, SAME |
| SIZES OR SHOW THE PROPOSED ALTERATIONS |
| ON THE PLAN. |
| |
| NOT ADDRESSED. |
| |
| 3.)PROVIDE THE BUILDING HEIGHT AND |
| DESIGN PRESSURE INFORMATION FBC1609. |
| |
| HEIGHT WAS PROVIDED.SEE #1 ABOVE. |
| SOME OPENINGS ARE NOT COMPLIANT FOR ZONE |
| 5 FOR THIS BUILDING HEIGHT, FBC TABLE |
| 1609B AND D.SAME COMMENT APPLIES; IF |
| PRODUCT WITH +-70 IS USED, THIS IS |
| COMPLIANT FOR ALL OPENINGS.CIRCLE ON |
| THE PRODUCT APPROVAL. |
| |
| 4.)THE NOTICE OF COMMENCEMENT PROVIDED |
| DOES NOT HAVE THE OWNER INFORMATION. |
| FS713.13. |
| |
| 5.)VALUATION APPEARS LOW.PROVIDE A |
| REASONABLE VALUE OF WORK OR AN ESTIMATE |
| WILL BE DONE FOR YOU USING MARSHALL & |
| SWIFT. - NOTE - ADJUSTED VALUE PER |
| CONTRACTOR |
| |
| NEW COMMENTS - |
| |
| 6.)THE NEW PLAN SUBMITTED SHOWS |
| MULLIONS.PLEASE PROVIDE PRODUCT |
| APPROVALS.IF THE MULLION PRODUCT |
| APPROVALS SHOW NONCOMPLIANT OPTIONS |
| BASED ON WIND PRESSURES FBC TABLE |
| 1609.6B AND D, CIRCLE WHICH PRODUCT YOU |
| WILL USE. |