2006-05-09 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 5-2-06
 NOTE #1 ENERGY CAL'S. NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) AS REQUESTED IN LAST REVIEW NOTE #2
 PLEASE SUBMIT 2 COPYS OF ALL PAPER WORK
 (NEED 2 COPYS OF PLANS).
  
 3) MASTER BEDROOM IS LISTED IN THE
 MANUAL J CAL'S. BUT NO PLANS HAVE BEEN
 SUBMITTED SHOWING THE MASTER BEDROOM,
 PLEASE SUBMIT.
  
 4) PLEASE SHOW CFM'S AT A/C GRILLS FOR
 OFFICE AND LIVING ROOM.
  
 5) PLEASE SHOW SIZE OF RIGID DUCT IN
 LIVING ROOM AND HALL-WAY.
  
 6) PLEASE SHOW SEER OF A/C SYSTEM ON
 PLANS.
  
 7) RETURN AIR TRANSFER GRILLS IN BEDROOM
 1 AND 2 ARE TO SMALL, SEE NOTE #8 (B).
  
 8)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  