Date |
Text |
2006-05-09 00:00:00 | *** DENIED *** |
| 1) AS REQUESTED IN LAST REVIEW 5-2-06 |
| NOTE #1 ENERGY CAL'S. NEED TO BE SIGNED |
| BY OWNER/AGENT. |
| |
| 2) AS REQUESTED IN LAST REVIEW NOTE #2 |
| PLEASE SUBMIT 2 COPYS OF ALL PAPER WORK |
| (NEED 2 COPYS OF PLANS). |
| |
| 3) MASTER BEDROOM IS LISTED IN THE |
| MANUAL J CAL'S. BUT NO PLANS HAVE BEEN |
| SUBMITTED SHOWING THE MASTER BEDROOM, |
| PLEASE SUBMIT. |
| |
| 4) PLEASE SHOW CFM'S AT A/C GRILLS FOR |
| OFFICE AND LIVING ROOM. |
| |
| 5) PLEASE SHOW SIZE OF RIGID DUCT IN |
| LIVING ROOM AND HALL-WAY. |
| |
| 6) PLEASE SHOW SEER OF A/C SYSTEM ON |
| PLANS. |
| |
| 7) RETURN AIR TRANSFER GRILLS IN BEDROOM |
| 1 AND 2 ARE TO SMALL, SEE NOTE #8 (B). |
| |
| 8)BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |
| |