2006-05-18 00:00:00 | | | | | DENIED | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | THE VALUE ON THE APPLICATION MUST | | INCLUDE THE TOTAL COST OF LABOR AND | | MATERIAL FOR THE GENERATOR , EQUIPMENT | | (TRANSFER SWITCHES, PANELS ETC.)AND PAD | | PER 108.3 FBC AS AMMENDED. | | | | PLEASE SUBMIT A SITE PLAN AND LOCATE ALL | | THE SERVICE AND GENERATOR GEAR ON SAME | | SO THAT COMPLIANCE WITH | | 230.72(GROUPING), 225.31-39 FOR THE | | DISCONNECTING MEANS REQUIREMENTS AND | | 250.32 FOR GROUNDING CAN BE REVIEWED. | | 225.36 SUITABLE FOR SERVICE EQUIPMENT. | | | | THE DISCONNECTING MEANS SPECIFIED IN | | 225.31 SHALL BE SUITABLE FOR USE AS | | SERVICE EQUIPMENT. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | |
|