2006-05-18 00:00:00 
  
 DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR , EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)AND PAD
 PER 108.3 FBC AS AMMENDED.
  
 PLEASE SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
 225.36 SUITABLE FOR SERVICE EQUIPMENT.
  
 THE DISCONNECTING MEANS SPECIFIED IN
 225.31 SHALL BE SUITABLE FOR USE AS
 SERVICE EQUIPMENT.
  