Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-16 00:00:001. SUITABLE ACCESS TO BE MAINTAINED WHEN
 WORK IS BEING ACCOMPLISHED FOR EMERGENCY
 SERVICES DELIVERY PURPOSES.
  
 2. THE REMOVAL OF THE UNDERGROUND
 STORAGE TANKS (UST'S) SHALL COMFORM WITH
 ALL APPLICABLE REGULATIONS AND NFPA 30.
  
 3. ALL OF THE FIRE SAFETY NOTES
 DISPLAYED ON G-1 SHALL BE FOLLOWED. ALL
 APPROPRIATE WARNING SIGNS WILL BE
 REQUIRED TO BE INSTALLED. (8-10)
  
 4. GASOLINE DISPENSERS HOSES SHALL NOT
 EXCCED THE REQUIRED LENGHTS AND BE
 EQUIPPED WITH THE APPROPRIATE BREAK-AWAY
 DEVICES.
  
 5. PLEASE ENSURE THAT RELOCATED
 EMERGENCY STOP DEVICE FOR THE FUEL AREAS
 IS PROPERLY IDENTIFIED.
  
 6. ALL ELECTRICAL WORK SHALL COMPLY WITH
 NFPA 70, THE NATIONAL ELECTRICAL CODE.
  
 7. APPROPRIATE FIRE EXTINGUISHING
 EQUIPMENT SHALL BE PRESENT AT FUEL
 DISPENSING LOCATIONS. COULD NOT LOCATE
 THIS INFORMATION ON THE DRAWINGS. PLEASE
 ADVISE.