Plan Review Notes
Plan Review Notes For Permit 06041060
Permit Number 06041060
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-17 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER AS REQUIRED UNDER FS 471.023.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS, ALL TITLE BLOCKS WHETHER OR NOT
 COMMENTS ARE MADE BYOTHER REIVEWER(S)>
  
 2) NOTE:PLEASE ALSO SEE THE REFERENCED
 FLORIDA ADMINISTRATIVE CODE AS ALL PLANS
 SIGNED , DATED AND SEALED BY SAID
 ENGINEER , SHALL CONTAIN TILE BOCKS WITH
 ALL INFORMATION AS REQUIRED.
  
 3) NOTE: PLEASE SEE THAT PLANS REFERENCE
 THE CURRENT CODES RELEVANT TO THIS
 PROJECT. PLEASE KNOW, PLANS MENTIONS THE
 "LATEST EDITION" OF THE NEC, HOWEVER
 PLEASE KNOW THE STATE OF FLORIDA IS
 STILL UNDER THE 2002 EDITION. PLEASE
 ADJUST ACCORDINGLY.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]