Plan Review Notes
Plan Review Notes For Permit 06041025
Permit Number 06041025
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)THE PLANS ARE TO BE SIGNED,
 FAC61G1-16 (AS WELL AS PREVIOUS
 DISCUSSIONS WITH THE FLORIDA BOARD OF
 ARCHITECTS).IF YOU FEEL THAT A STAMP
 IS THE EQUIVALENT OF A SIGNATURE AND IS
 ACCEPTABLE, PLEASE PROVIDE A LETTER
 STATING SUCH AND IT WILL BE FORWARDED TO
 THE BOARD FOR THEIR OPINION.OTHERWISE,
 PLEASE SIGN ALL SHEETS (MICHAEL KYLE
 HART, AR01605).
  
 3.)DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.)CONSTRUCTION TYPE, A1.1 AND FIRE
 PROTECTION CRITERIA DECLARE TYPE II.
 THIS SHOULD BE TYPE IIA OR TYPE IIB,
 FBC6.
  
 5.)ARCHITECTURAL KEYNOTES, A5.1 DO NOT
 INCLUDE 5 AND 6.CODE COMPLIANCE CANNOT
 BE DETERMINED AS SCOPE OF WORK IS NOT
 CLEAR.
  
 6.)M0.1 REFERS TO INCORRECT BUILDING
 CODES.FOR EXAMPLE, FBC2003 IS NOT (AND
 NEVER WAS) THE GOVERNING CODE.CHECK
 ALL REFERENCES AND REVISE.