Plan Review Notes For Permit 06041011 |
Permit Number |
06041011 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-04 00:00:00 | *** DENIED *** | | 1) PLEASE SHOW ON MECHANICAL PLANS PAGE | | M-1 WHERE THE MAIN RETURN AIR DUCT WITH | | FIRE DAMPER PENETRATES THE FIRE WALL. | | | | 2) PLEASE SHOW ON MECHANICAL PLANS PAGE | | M-2 CONDENSING UNIT MOUNTING DETAILS, | | THAT THESE APPLICATIONS COMPLY WITH THE | | 2004 FBC 1609 AND WITH-STANDS WIND | | SPEEDS OF 140 MPH. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|