Plan Review Notes
Plan Review Notes For Permit 06041010
Permit Number 06041010
Review Stop M
Sequence Number 2
Notes
Date Text
2006-05-03 00:00:00*** DENIED ***
 1)CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 . PLEASE NOTE SUFFICIENT CLARITY MEANS
 THAT I SHOULD BE ABLE TO TELL WHAT WORK
 AND MATERIALS ARE TO BE USED BY THE
 PLANS SUBMITTED.
  
 2) AS NOTED IN LAST REVIEW 4-27-06 #2,
 PLANS NEED JOB ADDRESS ON ALL SHEETS
 (PLEASE SHOW THE CORRECT ADDRESS).
  
 3) AS NOTED IN LAST REVIEW 4-27-06 #3
 DESIGN, ARE THE T'S, Y'S, AND +'S MIXING
 BOXES, SEE NOTE #1.
  
 4) CFM'S HAVE BEEN WHITED OUT, CFM'S
 NEED TO BE ON PLANS AT EACH GRILL.
  
 5) SHOW SIZE OF EACH RETURN AIR TRANSFER
 GRILL ON PLANS.
  
 6) SHOW SIZE OF RETURN AIR GRILL TO AHU
 AND DUCT SIZE IF USED.
  
 7) PLEASE SEE NOTE #1, THANK YOU.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  