Plan Review Notes For Permit 06041010 |
Permit Number |
06041010 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-03 00:00:00 | *** DENIED *** | | 1)CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 | | . PLEASE NOTE SUFFICIENT CLARITY MEANS | | THAT I SHOULD BE ABLE TO TELL WHAT WORK | | AND MATERIALS ARE TO BE USED BY THE | | PLANS SUBMITTED. | | | | 2) AS NOTED IN LAST REVIEW 4-27-06 #2, | | PLANS NEED JOB ADDRESS ON ALL SHEETS | | (PLEASE SHOW THE CORRECT ADDRESS). | | | | 3) AS NOTED IN LAST REVIEW 4-27-06 #3 | | DESIGN, ARE THE T'S, Y'S, AND +'S MIXING | | BOXES, SEE NOTE #1. | | | | 4) CFM'S HAVE BEEN WHITED OUT, CFM'S | | NEED TO BE ON PLANS AT EACH GRILL. | | | | 5) SHOW SIZE OF EACH RETURN AIR TRANSFER | | GRILL ON PLANS. | | | | 6) SHOW SIZE OF RETURN AIR GRILL TO AHU | | AND DUCT SIZE IF USED. | | | | 7) PLEASE SEE NOTE #1, THANK YOU. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | | | |
|