Plan Review Notes
Plan Review Notes For Permit 06041010
Permit Number 06041010
Review Stop M
Sequence Number 1
Notes
Date Text
2006-04-27 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) PLANS NEED JOB ADDRESS, CONTRACTOR'S
 INFORMATION WITH LISENSE NUMBER ON ALL
 PAGES.
  
 3) FROM THE DESIGN OF YOURR SUBMITTED
 PLANS IT CAN NOT BE DETERMINED IF THE
 DUCT SYSTEM IS A TRUNK LINE, FLEX, OR
 WATER LINES, PLEALE CORRECT.
  
 4) WHEN DESIGNING THE DUCT SYSTEM SHOW
 THE SIZE OF ALL DUCTS.
  
 5) PORVIDE RETURN AIR FOR BEDROOMS.
 BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 6) SUBMIT TWO COPYS OF ALL PAPER WORK.
  
 7) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  