Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop M
Sequence Number 8
Notes
Date Text
2007-05-03 15:55:16--------------DENIED-----------------
  
 THE CHANGES SHOWN ON PLANS APPEAR TO ADEQUATELY ADDRESS
 THE OUTSTANDING CONDENSATE DISPOSAL ISSUES. HOWEVER,
 THE CONDENSATE CHANGES HAVE BEEN INCORPORATED ONTO THE
 SAME MECHANICAL PAGES WHICH WERE REJECTED DURING THE
 PREVIOUS MECHANICAL PLAN REVIEW WHICH WAS COMPLETED ON
 4/20/07. THESE PAGES CAN NOT BE APPROVED UNTILL ALL
 PLAN REVIEW COMMENTS RELATED TO THESE PAGES HAVE BEEN
 ADDRESSED. IF THE CONDENSATE CHANGES HAD BEEN
 INCORPORATED ONTO THE CURRENT PERMITTED SET OF PLANS,
 THE CONDENSATE CHANGES COULD HAVE BEEN APPROVED
 INDEPENDENT OF THE PREVIOUS REVISION WITH THE
 OUTSTANDING COMMENTS. AT THIS TIME YOU MAY EITHER
 RESUBMIT THE CONDENSATE CHANGES ON PLANS WHICH
 OTHERWISE MATCH THE CURRENT PERMITTED SET OF PLANS OR
 YOU MAY RESUBMIT THE CONDENSATE REVISIONS IN
 CONJUNCTION WITH RESPONSES TO THE OUTSTANDING
 COMMENTS.
  
  