Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop M
Sequence Number 5
Notes
Date Text
2006-12-11 10:17:14REVISION:
  
 SHEETS H0.02, H1.01 ARE APPROVED.THE RESPONSE LETTER
 SUBMITTED AHA CONSULTING ENGINEERS, INC. COMMENTS 1, 2,
 3, & 15 ARE ACCEPTABLE.
  
 PROVISO:
 PLEASE PROVIDE ADDTIONAL INFORMATION FOR THE
 FOLLOWING:
 H0.03 - DETAIL #26 CONDENSING UNIT MOUNTING DETAIL. THE
 DETAIL DOES NOT PROVIDE SPECIFIC INFORMATION FOR
 ANCHORING, IT ONLY PROVIDES A NOTE THAT THE UNIT LEGS
 ARE TO BE BOLTED TO CONCRETE PAD.PLEASE INDICATE BOLT
 SIZE.
  
 RESPONSE LETTER - COMMENT 6 WITH REGARDS TO THE
 CONDENSING UNITS LOCATED IN THE GARAGE AREA. RESPONSE
 INDICATES A MEMO FROM TRANE STATING THE INSTALLATION OF
 CONDENSING UNITS IN THE GARAGE IS ACCEPTABLE.THIS
 MEMO WAS NOT SUBMITTED TO THE CITY OF WEST PALM BEACH
 IN THE REVISION PACKAGE.
  
 RESPONSE LETTER COMMENT 7 & 8, CO SENSORS HAVE BEEN
 PROVIDED IN STORAGE AREAS THAT ARE TRANSFERING AIR FROM
 THE GARAGE FOR VENTILATION PURPOSES.THE GENERAL
 DRAWING NOTE ON SHEETS H1.02, H1.03, H1.05,IT STATES
 THE SENSORS ARE TO BE INSTALLED PER MANUFACTURER'S
 INSTRUCTION.PLEASE NOTE, CO SENSORS ARE TO BE SET TO
 ACTIVATE VENTILATION SYSTEM AT A MAXIMUM OF 25 PPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].