Plan Review Notes For Permit 06040957 |
Permit Number |
06040957 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2006-12-11 10:17:14 | REVISION: | | | | SHEETS H0.02, H1.01 ARE APPROVED.THE RESPONSE LETTER | | SUBMITTED AHA CONSULTING ENGINEERS, INC. COMMENTS 1, 2, | | 3, & 15 ARE ACCEPTABLE. | | | | PROVISO: | | PLEASE PROVIDE ADDTIONAL INFORMATION FOR THE | | FOLLOWING: | | H0.03 - DETAIL #26 CONDENSING UNIT MOUNTING DETAIL. THE | | DETAIL DOES NOT PROVIDE SPECIFIC INFORMATION FOR | | ANCHORING, IT ONLY PROVIDES A NOTE THAT THE UNIT LEGS | | ARE TO BE BOLTED TO CONCRETE PAD.PLEASE INDICATE BOLT | | SIZE. | | | | RESPONSE LETTER - COMMENT 6 WITH REGARDS TO THE | | CONDENSING UNITS LOCATED IN THE GARAGE AREA. RESPONSE | | INDICATES A MEMO FROM TRANE STATING THE INSTALLATION OF | | CONDENSING UNITS IN THE GARAGE IS ACCEPTABLE.THIS | | MEMO WAS NOT SUBMITTED TO THE CITY OF WEST PALM BEACH | | IN THE REVISION PACKAGE. | | | | RESPONSE LETTER COMMENT 7 & 8, CO SENSORS HAVE BEEN | | PROVIDED IN STORAGE AREAS THAT ARE TRANSFERING AIR FROM | | THE GARAGE FOR VENTILATION PURPOSES.THE GENERAL | | DRAWING NOTE ON SHEETS H1.02, H1.03, H1.05,IT STATES | | THE SENSORS ARE TO BE INSTALLED PER MANUFACTURER'S | | INSTRUCTION.PLEASE NOTE, CO SENSORS ARE TO BE SET TO | | ACTIVATE VENTILATION SYSTEM AT A MAXIMUM OF 25 PPM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|