2006-10-31 15:15:12 | |
| *** ISSUED PERMIT*** |
| -PLAN REVIEW HISTORY- |
| |
| PERMIT# 06040957 |
| ADDRESS: 525 OKEECHOBEE BLVD. |
| CONT: CENTEX CONSTRUCTION |
| TELL # (954)214-9415 |
| |
| THE ATTACHED COMMENTS ARE PART OF THE |
| PERMIT AND PLAN REVIEW PACKAGE AND ARE |
| NOT TO BE REMOVED FROM THE ISSUED SET |
| OF PLANS.104.2.1.2 ADMINISTRATIVE CODE. |
| |
| BUILDING PROVISO: |
| 1)A SEPERATE PERMIT WILL BE REQUIRED FOR THE NORTH |
| ELEVATOR TOWER, A ISSUED PERMIT & PLANS TO BE REQUIRED |
| WITHIN 60DAYS. |
| |
| 2) PLANS ARE TO BE REVISED TO INDICATE A PRODUCT OTHER |
| THAN MCM PANELS, |
| A 60 DAY PERIOD WILL BE PROVIDED FOR THE CONTRACTOR AND |
| DESIGN TEAM |
| TO REVIEW THE NEW PRODUCT FOR CODE COMPLIANCE FOR FIRE |
| AND WIND. |
| 12-04-06 CITY HAS FL APPROVAL FOR FIRE RESISTANCE FL |
| 2661-R1 ALUCOBOND PLUS. |
| |
| 3) PLANS ALSO INDIICATE THE USE OF ALUMINUM EXTRUSIONS, |
| SHOP DRAWING |
| WILL BE REQUIRED INDICATING THE SIZE, AND CONDITIONS |
| FOR ANCHORING OF PANELS. |
| SHOP DRAWINGS FOR ALUMINIUM EXTRUSIONS REVIEWED 3-01-07 |
| JW |
| |
| |
| 4) PRODUCT APPROVALS A 60 DAY PERIOD OF TIME WILL BE |
| PROVIDED FOR THE |
| CONTRACTOR & DESIGN TEAM TO SUBMIT PRODUCT APPROVALS |
| FOR HOLLOW METAL DOORS |
| THAT WILL MEET THE LARGE MISSLE IMPACT IF REQUIRED, AND |
| WIND. |
| 12-04-06 COMPLIED MIAMI-DADE 04-0604.02 |
| |
| 5) 12-04-06 CITY IS IN RECEIPT OF SIGNED & SEALED WIND |
| REPORT. THE WIND STUDY REPORT SUBMITTED IS NOT SIGNED |
| NOR SEALED. |
| IF THE 3 SETS OF WIND REPORTS |
| SIGNED AND SEALED ARE NOT SUBMITTED FOR PUBLIC RECORD |
| WITH |
| IN A WEEK THE WIND CALCULATIONS WILL NEED TO BE |
| ADDRESSED UNDER ASCE 7-02. BUILDING PLAN REVIEW JIM |
| WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |