2006-10-26 15:23:41 | THANK YOU FOR THE RESPONSE LETTER (SEPT 26,2006) |
| ADDRESSING COMMENTS FROM THE MECHANICAL PLAN REVIEW. |
| PLEASE NOTE, FURTHER CLARIFICATION IS REQUIRED FOR THE |
| FOLLOWING ITMES: |
| |
| RESPONSE TO COMMENT 1:PLAN SHEET H0.03 REVISED DETAIL |
| 25 FOR THE ACCU 1 & 2. |
| |
| PLEASE CLARIFYTHE CONCRETE SLABFOR THE CONDENSING |
| UNIT ON THE ROOF TOP.PLEASE SPECIFY THE ROOF MATERIAL |
| THIS SLAB WILL BE SETTING ON.IT APPEARS THESE UNITS |
| ARE ACTUALLY INSTALLED IN THE GARAGE AREAS. |
| |
| |
| RESPONSE TO COMMENT 2:PLANS SHEET H0.03 REVISED |
| DETAIL 26.THE RESPONSE INDICATES THE CURB WILL BE 18" |
| HIGH. |
| |
| ACCORDING TO THE DETAIL THE 18" DEMINSION IS THE |
| CLEARANCE BETWEEN THE ROOF SURFACE AND THE BOTTOM OF |
| THE ACCU.IS THESE CURBS "PATE CURBS"WILL THE |
| FLASHING HAVE TO EXTEND UNDERNEATH THE ACCU?PLEASE |
| NOTE, THE CLEARANCE BETWEEN THE ROOF SURFACE AND THE |
| BOTTOM OF ACCU IS DETERMINED BY THE WIDTH OF THE UNIT |
| IN ACCORDANCE WITH 2004 FBE 1509.7. |
| |
| |
| RESPONSE TO COMMENT 3:PLAN SHEET H1.01 INDICATES THE |
| TERMINATION OF CIF-6 IS 10 FT ABOVE GRADE. |
| |
| PLEASE NOTE, THE EXHAUST FROM THIS IS FROM THE LOADING |
| DOCK FOR THE REMOVAL OF CARBON MONOXIDE.PER 2004 FMC |
| 401.5.1HAZAROUS OR NOXIOUS CONTAMINANT SHALL BE LOCATED |
| A MINIMUM OF 10 FROM OPENINGS.PER 501.2 AIR REMOVED |
| BY EVERY MECHANICAL EXHAUST SHALL DISCHARGE OUTDOORS AT |
| A POINT WHERE IT WILL NOT CAUSE A NUISANCE.BY |
| DEFINITION A NUISANCE IS CONSIDERED THAT WHICH IS |
| DETRIMENTAL TO HEALTH, WHICH CARBON MONOXIDE IS. |
| |
| |
| RESPONSE TO COMMENT 4 & 5 WERE ADDRESSED. |
| |
| COMMENT 6 WAS NOT ADDRESSED:PLAN SHEET H1.02, H1.03, |
| & H1.05, PLEASE INDICATE IF THE CONDENSING UNITS ARE |
| LOCATED IN SIDE THE GARAGE AREA.PLEASE PROVIDE |
| INSTALLATION INSTRUCTIONS INDICATING THIS IS ACCEPTABLE |
| TO THE MANUFACTURER. |
| |
| |
| COMMENT 7 & 8 WERE NOT ADDRESSED:VENTILATION FOR THE |
| STORAGE AREAS - PER OUR CONVERSATION, CO SENSORS ARE TO |
| BE INSTALLED INTO NON-HABITABLE SPACES WHEN THE MAKE-UP |
| AIR BEING PROVIDED IS ACHIEVED THROUGH THE GARAGE |
| SPACE. |
| |
| COMMENT 9 THROUGH 14 WERE ADDRESSED. |
| |
| |
| |
| NEW COMMENTS: |
| PLEASE NOTE, SMOKE, FIRE AND OR COMBINATION DAMPERS MAY |
| BE REQUIRED IN THE FUTURE TENANT BUILDOUT DEPENING ON |
| THE OCCUPANCIES. |
| |
| |