2006-09-25 00:00:00***** PLEASE KNOW AS OF 9/25/06
 MECHANICAL REVIEW NOTES NOT COMPLETE,
 PLANS MAY BE PICKED , HOWEVER PLEASE BE
 AWARE NOTES FOR MECHANICAL MAY FOLLOW.
2006-09-21 00:00:00DENIED:
 1.PLAN SHEET H0.03 DETAIL 26 - ROOFTOP
 MOUNTING DETAIL FOR THE CONDENSING UNIT
 DOES NOT COMPLY WITH 2004 FBC 1509.7.
  
 2.PLAN SHEET H0.03 DETAIL 30 - CURB
 DETAIL DOES NOT SPECIFY HEIGHT OF THE
 CURB.PER 2004 FBC 1509.7, RAISED CURBS
 SHALL BE A MINIMUM OF 8" ABOVE THE ROOF
 SURFACE.
  
 3.H1.01 EXHAUST TERMINATION FROM CIF-6
 IS 5' X 3' LOUVER OVER A DOOR.PER 2004
 FMC 401.5.2 EXHAUST AIR SHALL BE LOCATED
 AS NOT TO CREATE A NUISANCE, AIR SHALL
 NOT BE DIRECTED ONTO WALKWAYS.
  
 4.PLAN SHEET H1.02, CO SENSORS ARE
 INDICATED, PLAN DOES NOT SPECIFY AT WHAT
 PARTS PER MILLION (PPM).PER 2004 FMC
 404.1, A MAXIMUM OF 25 PPM IS THE
 REQUIREMENT FOR THE ACTIVATION OF THE
 FANS.
  
 5.PLAN SHEET H1.02 PF-1 & 2 GARAGE
 EXHAUST, PLEASE CLARIFY AIR MAKE-UP FOR
 EACH FLOOR.PLEASE PROVIDE
 CALCULATIONS.CO SENSORS SHALL BE TIED
 TO THE EMERGENCY POWER.
  
 6.PLAN SHEET H1.02 PLEASE INDICATE IF
 THE CONDENSING UNITS ARE LOCATED INSIDE
 OR OUTDOORS.
  
 7.PLAN SHEET H1.03 CIF-3 EXHAUST FAN
 FROM STORAGE ROOM 304 TERMINATES INTO
 THE GARAGE INSTEAD OF THE OUTDOORS AS
 REQUIRED BY 2004 FMC 501.2
  
 8.PLAN SHEET H1.03, H1.05PLEASE
 CLARIFY STORAGE (RMS 302,402,502)
 MAKE-UP AIR FROM THE GARAGE AREA &
 EXHAUST TERMINATES INTO THE GARAGE AREA
 ALSO.
  
 9.PLAN SHEET H1.06 RM 614 INDICATES A
 6"X6" SUPPLY DUCT PENETRATING THE 1 HR
 PARTITION.PLEASE NOTE, DUCT SHALL
 COMPLY WITH THE EXCEPTIONS IN FMC
 607.5.3 OF THE 2004 CODE OR INSTALL A
 FIRE DAMPER.PLEASE CLARIFY.
  
 9.PLAN SHEET H1.17 INDICATES 4 FT
 STEEL DUNNAGE, PLEASE PROVIDE DETAIL OF
 THE SUPPORT ANCHORING TO THE ROOF,
 CLEARANCE BETWEEN THE ROOF SURFACE AND
 SUPORT RAIL, AND THE ACHORING OF SPRING
 ISOLATORS TO THE STEEL.
  
 11. PLAN SHEET H1.18 & DETAIL 26 ON PLAN
 SHEET H0.03.SUPPORTS FOR ACCU1
 & ACCU2 ON SLEEPERS.PER 2004 FBC
 1509.7ROOF MOUNTED EQUIPMENT WHERE
 ROOFING MATERIALS ARE UNDERNEATH THE
 EQUIPMENT A ROOF STAND IS REQUIRED IN
 ACCORDANCE WITH TABLE 1509.PLEASE SHOW
 THE ANCHORING DETAILS.
  
 12. PLEASE PROVIDE SUBMITTALS FOR
 EQUIPMENT.
  
 13. PROVIDE INFORMATION ABOUT THE
 EMERGENCY GENERATOR.PLEASE INDICATE
 FUEL TYPE & STORAGE.PROVIDE
 VENTILATION INFORMATION SHOULD THE
 GENERATOR BE LOCATED INSIDE THE
 BUILDING.
  
 14. PLANS ARE TO BE SIGNED, SEALED, AND
 DATED BY THE ENGINEER IN ACCORDANCE WITH
 FS 471.025 & FAC 61G15-23.002.
  