2006-09-25 00:00:00 | ***** PLEASE KNOW AS OF 9/25/06 |
| MECHANICAL REVIEW NOTES NOT COMPLETE, |
| PLANS MAY BE PICKED , HOWEVER PLEASE BE |
| AWARE NOTES FOR MECHANICAL MAY FOLLOW. |
2006-09-21 00:00:00 | DENIED: |
| 1.PLAN SHEET H0.03 DETAIL 26 - ROOFTOP |
| MOUNTING DETAIL FOR THE CONDENSING UNIT |
| DOES NOT COMPLY WITH 2004 FBC 1509.7. |
| |
| 2.PLAN SHEET H0.03 DETAIL 30 - CURB |
| DETAIL DOES NOT SPECIFY HEIGHT OF THE |
| CURB.PER 2004 FBC 1509.7, RAISED CURBS |
| SHALL BE A MINIMUM OF 8" ABOVE THE ROOF |
| SURFACE. |
| |
| 3.H1.01 EXHAUST TERMINATION FROM CIF-6 |
| IS 5' X 3' LOUVER OVER A DOOR.PER 2004 |
| FMC 401.5.2 EXHAUST AIR SHALL BE LOCATED |
| AS NOT TO CREATE A NUISANCE, AIR SHALL |
| NOT BE DIRECTED ONTO WALKWAYS. |
| |
| 4.PLAN SHEET H1.02, CO SENSORS ARE |
| INDICATED, PLAN DOES NOT SPECIFY AT WHAT |
| PARTS PER MILLION (PPM).PER 2004 FMC |
| 404.1, A MAXIMUM OF 25 PPM IS THE |
| REQUIREMENT FOR THE ACTIVATION OF THE |
| FANS. |
| |
| 5.PLAN SHEET H1.02 PF-1 & 2 GARAGE |
| EXHAUST, PLEASE CLARIFY AIR MAKE-UP FOR |
| EACH FLOOR.PLEASE PROVIDE |
| CALCULATIONS.CO SENSORS SHALL BE TIED |
| TO THE EMERGENCY POWER. |
| |
| 6.PLAN SHEET H1.02 PLEASE INDICATE IF |
| THE CONDENSING UNITS ARE LOCATED INSIDE |
| OR OUTDOORS. |
| |
| 7.PLAN SHEET H1.03 CIF-3 EXHAUST FAN |
| FROM STORAGE ROOM 304 TERMINATES INTO |
| THE GARAGE INSTEAD OF THE OUTDOORS AS |
| REQUIRED BY 2004 FMC 501.2 |
| |
| 8.PLAN SHEET H1.03, H1.05PLEASE |
| CLARIFY STORAGE (RMS 302,402,502) |
| MAKE-UP AIR FROM THE GARAGE AREA & |
| EXHAUST TERMINATES INTO THE GARAGE AREA |
| ALSO. |
| |
| 9.PLAN SHEET H1.06 RM 614 INDICATES A |
| 6"X6" SUPPLY DUCT PENETRATING THE 1 HR |
| PARTITION.PLEASE NOTE, DUCT SHALL |
| COMPLY WITH THE EXCEPTIONS IN FMC |
| 607.5.3 OF THE 2004 CODE OR INSTALL A |
| FIRE DAMPER.PLEASE CLARIFY. |
| |
| 9.PLAN SHEET H1.17 INDICATES 4 FT |
| STEEL DUNNAGE, PLEASE PROVIDE DETAIL OF |
| THE SUPPORT ANCHORING TO THE ROOF, |
| CLEARANCE BETWEEN THE ROOF SURFACE AND |
| SUPORT RAIL, AND THE ACHORING OF SPRING |
| ISOLATORS TO THE STEEL. |
| |
| 11. PLAN SHEET H1.18 & DETAIL 26 ON PLAN |
| SHEET H0.03.SUPPORTS FOR ACCU1 |
| & ACCU2 ON SLEEPERS.PER 2004 FBC |
| 1509.7ROOF MOUNTED EQUIPMENT WHERE |
| ROOFING MATERIALS ARE UNDERNEATH THE |
| EQUIPMENT A ROOF STAND IS REQUIRED IN |
| ACCORDANCE WITH TABLE 1509.PLEASE SHOW |
| THE ANCHORING DETAILS. |
| |
| 12. PLEASE PROVIDE SUBMITTALS FOR |
| EQUIPMENT. |
| |
| 13. PROVIDE INFORMATION ABOUT THE |
| EMERGENCY GENERATOR.PLEASE INDICATE |
| FUEL TYPE & STORAGE.PROVIDE |
| VENTILATION INFORMATION SHOULD THE |
| GENERATOR BE LOCATED INSIDE THE |
| BUILDING. |
| |
| 14. PLANS ARE TO BE SIGNED, SEALED, AND |
| DATED BY THE ENGINEER IN ACCORDANCE WITH |
| FS 471.025 & FAC 61G15-23.002. |
| |