2006-05-01 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| |
| FOUNDATION PLUMBING PERMIT |
| |
| 1. SHT P-1 1" DRAIN FROM METAL PAN ABOVE |
| ELECTRICAL ROOM STILL SHOWN. METAL PAN |
| HAS BEEN REMOVED. PLEASE CLARIFY. |
| SECTION 106.1.1. |
| |
| 2. SUBMIT A STORM RISER DIAGRAM THAT |
| REFLECT THE PIPING SHOWN ON SHT P-10 AND |
| ALL RWL RISERS. SHOW ALL PIPE SIZES, |
| SLOPE OF PIPE ETC. SECTION 106.1.5.1.3. |
| |
| 3. SHT P-15 GREASE WASTE ISOMETRIC |
| DIAGRAM RISER FLOOR SINK REQUIRED AT P/5 |
| DOWNSTREAM OF HUB DRAIN TO REFLECT THE |
| FLOOR PLAN. SECTION 106.1.1. |
| |
| 4. SEE COMMENTS 5, 7, 9, 15, 17, 18, 19, |
| AND 31 FROM SECOND REVIEW OF BUILDING |
| PERMIT APPLICATION FOR ISSUES THAT MAY |
| AFFECT THE PIPING IN THE FIRST FLOOR |
| SLAB. |
| |
| 5. SECTION 105.13 THE HOLDER OF A PHASED |
| PERMIT FOR THE FOUNDATION OR OTHER PARTS |
| OF A BUILDING OR STRUCTURE SHALL PROCEED |
| AT THE HOLDER'S OWN RISK WITH THE |
| BUILDING OPERATION AND WITHOUT ASSURANCE |
| THAT A PERMIT FOR THE ENTIRE STRUCTURE |
| WILL BE GRANTED. CORRECTIONS MAY BE |
| REQUIRED TO MEET THE REQUIREMENTS OF THE |
| TECHNICAL CODES. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |