2006-05-01 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 FOUNDATION PLUMBING PERMIT
  
 1. SHT P-1 1" DRAIN FROM METAL PAN ABOVE
 ELECTRICAL ROOM STILL SHOWN. METAL PAN
 HAS BEEN REMOVED. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 2. SUBMIT A STORM RISER DIAGRAM THAT
 REFLECT THE PIPING SHOWN ON SHT P-10 AND
 ALL RWL RISERS. SHOW ALL PIPE SIZES,
 SLOPE OF PIPE ETC. SECTION 106.1.5.1.3.
  
 3. SHT P-15 GREASE WASTE ISOMETRIC
 DIAGRAM RISER FLOOR SINK REQUIRED AT P/5
 DOWNSTREAM OF HUB DRAIN TO REFLECT THE
 FLOOR PLAN. SECTION 106.1.1.
  
 4. SEE COMMENTS 5, 7, 9, 15, 17, 18, 19,
 AND 31 FROM SECOND REVIEW OF BUILDING
 PERMIT APPLICATION FOR ISSUES THAT MAY
 AFFECT THE PIPING IN THE FIRST FLOOR
 SLAB.
  
 5. SECTION 105.13 THE HOLDER OF A PHASED
 PERMIT FOR THE FOUNDATION OR OTHER PARTS
 OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE
 BUILDING OPERATION AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE ENTIRE STRUCTURE
 WILL BE GRANTED. CORRECTIONS MAY BE
 REQUIRED TO MEET THE REQUIREMENTS OF THE
 TECHNICAL CODES.
  