Plan Review Notes For Permit 06040937 |
Permit Number |
06040937 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-06-30 00:00:00 | RE SUB | | | | SHT. 6.1 PROVISO: | | | | 3) SHT 6.1 PLUMBING NOTES. #15 REFERENCE | | AIR CHAMBERS. TO COMPLY WITH ASSE 1010. | | SEE SEC 604.9 WATER HAMMER ARRESTORS. | | | | 4) SHT 3.1SHOW LOCATION OF WATER | | HEATER, PROVIDE A DETAIL TO SHOW | | COMPLIANCE OF SEC 604.7 FOR THERMAL | | EXPANSION. | | | | 5) SHT 6.1 WATER RISER. SEC 606.1 (4) | | LOCATION OF FULLY OPEN VALVES. | | SOV REQUIRED ON THE TOP OF EVERY WATER | | DOWN FEED PIPE. | | | | 6) SHT 6.1 WATER RISER, SHOW LOCATION OF | | BACK FLOW PREVENTER AS REQUIRED BY | | LOCAL ORDINANCE #2853-95 |
|