Plan Review Notes
Plan Review Notes For Permit 06040937
Permit Number 06040937
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-27 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1)SEE OTHER PLAN REVIEW COMMENTS,
 THAT MAY EFFECT PLUMBING PLAN REVIEW.
  
 2) SHT 3.1 LOUNGE SINK SEC 11-4.24
  
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER
 OR RIM NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 3) SHT 6.1 PLUMBING NOTES. #15 REFERENCE
 AIR CHAMBERS. TO COMPLY WITH ASSE 1010.
 SEE SEC 604.9 WATER HAMMER ARRESTORS.
  
 4) SHT 3.1SHOW LOCATION OF WATER
 HEATER, PROVIDE A DETAIL TO SHOW
 COMPLIANCE OF SEC 604.7 FOR THERMAL
 EXPANSION.
  
 5) SHT 6.1 WATER RISER. SEC 606.1 (4)
 LOCATION OF FULLY OPEN VALVES.
 SOV REQUIRED ON THE TOP OF EVERY WATER
 DOWN FEED PIPE.
  
 6) SHT 6.1 WATER RISER, SHOW LOCATION OF
 BACK FLOW PREVENTER AS REQUIRED BY
 LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS QUESTIONS 561- 805-6692