Plan Review Notes
Plan Review Notes For Permit 06040937
Permit Number 06040937
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-17 00:00:00****** UNSAT *******
  
 1) NOTE: PLEASE SUBMIT PLANS DONE BY A
 MIN OF AN ARCHITECT PER FS 481.229 FOR
 VALUE AND SCOPE OF WORK OVER $25,000.
  
 2) NOTE: PLEASE PROVIDE THE RISER
 DIAGRAM, AS PLANS SEEM TO SHOW TWO
 DIFFERENT METERS ??. THIS IS BEING SHOWN
 AS A SINGLE OCCUPANCY BUILDING AND NO
 "FIRE WALL" SEPARATION IS PRESENT ON
 PLANS. PLEASE KNOW, ONLY ONE SERVICE
 WILL BE PERMITTED AND ALL MAINS SHALL BE
 GROUPED. 230.2,230.70,230.72
  
 3) NOTE: PLEASE SEE 517 AND INDICATE
 LOCATIONS AND WIRING METHODS AS SET
 FORTH IN THE 2002 NEC AND LS CODE.
 PLEASE SEE ALL OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY ALSO AFFECT THIS.
  
 4)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT LTS.
  
 5) NOTE: PLEASE SEE THE MIN OCP AND AWG
 FOR EXISTING AHU'S SHALL BE ADJUSTED
 EVEN IF EXISITNG. PLEASE SEE
 424.3B,240.4,310.16 10KW, #8 AND 50A
 OCP.
  
 6) NOTE: PLEASE SUPPLY LOAD CALCUALTIONS
 PER 220.3,220.10,220.11,220.13 ETC.
 PLEASE SEE 215.3,230.42 FOR ALL
 CONTINUOUS LOADS TO BE SHOWN AT 125%.
  
 7) NOTE: PLANS SHALL CONTAIN THE CURRENT
 CODES UNDER ADOPTION BY THE STATE OF
 FLORIDA.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72 ETC.
  
 8) NOTE: PLEASE SEE BUIDLIGN REVIEW
 COMMENTS FOR REQUIRED "STATEMENT" ON
 PLANS FOR THE DESIGN PROFESSIONAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  