Notes |
Date |
Text |
2006-05-04 00:00:00 | THE VALUE ON THE APPLICATION MUST | | INCLUDE THE TOTAL COST OF LABOR AND | | MATERIAL FOR THE GENERATOR , EQUIPMENT | | (TRANSFER SWITCHES, PANELS ETC.)AND PAD | | PER 108.3 FBC AS AMMENDED. | | | | PLEASE SUBMIT A SITE PLAN AND LOCATE ALL | | THE SERVICE AND GENERATOR GEAR ON SAME | | SO THAT COMPLIANCE WITH | | 230.72(GROUPING), 225.31-39 FOR THE | | DISCONNECTING MEANS REQUIREMENTS AND | | 250.32 FOR GROUNDING CAN BE REVIEWED. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|