Plan Review Notes For Permit 06040851 |
Permit Number |
06040851 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-03 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING | | INFORMATION REQUIRED FOR PLAN REVIEW: | | | | 1. FBC-2004 SEC. 424.2.6.6 ENTRAPMENT | | PROTECTION FOR SUCTION INLETS. PLEASE | | SUBMIT AN ENGINEERED TABLE FOR "VENT | | PIPE MAXIMUM LENGTH" INDICATING PUMP | | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH | | OF 1" PVC VENT PIPE, FROM WHERE IT | | STARTS TO WHERE IT ENDS UP, COMPLYING | | WITH THREE SECOND RELEASE. | | | | 2. FBC-2001424.2.6.6.5 WHERE PROVIDED, | | THE VACUUM OR PRESSURE CLEANER FITTING | | SHALL BE LOCATED AT LEAST 6" AND NOT | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | THE SKIMMER. ( NEED MANUFACTURE CUT | | SHEET OF VACUUM OR PRESSURE CLEANING | | FITTING OR ADD MAKE AND MODEL NUMBER TO | | PRINT) | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS |
|