2006-05-03 00:00:00******DENIED******
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1. FBC-2004 SEC. 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF 1" PVC VENT PIPE, FROM WHERE IT
 STARTS TO WHERE IT ENDS UP, COMPLYING
 WITH THREE SECOND RELEASE.
  
 2. FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. ( NEED MANUFACTURE CUT
 SHEET OF VACUUM OR PRESSURE CLEANING
 FITTING OR ADD MAKE AND MODEL NUMBER TO
 PRINT)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS