2006-08-18 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS NEED TO BE
 MADE TO THE SANITARY ISOMETRIC RISER
 DIAGRAM ON SHEET A-3. NOTE: CORRECTIONS
 ARE MADE IN RED INK.
  
 1. PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: THE WASTE PIPE TO THE KITCHEN SINK
 IS WRONG, PLEASE REFERENCE THE CORRECTED
 DRAWING ON SHEET A-3 FOR RESUBMITTAL.
 2. PLEASE INDICATE THE DISHWASHER DRAIN
 TO THE KITCHEN SINK ON SHEET A-3.
 3. THE BIDET INDICATED ON SHEET A-3
 SHALL BE TRAPPED PER 1002.1 AND SHALL BE
 SIZED PER TABLE 709.1, PLEASE REFERENCE
 THE CORRECTED DRAWING ON SHEET A-3.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS