Plan Review Notes
Plan Review Notes For Permit 06040846
Permit Number 06040846
Review Stop P
Sequence Number 3
Notes
Date Text
2006-07-18 00:00:00******DENIED 3RD TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW:
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL. NOTE: THE SANITARY
 ISOMETRIC RISER DIAGRAM INDICATED ON
 SHEET A-3 DOES NOT REFLECT THE FLOOR
 PLAN, BEING THAT THE FLOOR PLAN HAS
 CHANGED SINCE THE LAST RESUBMITTAL. THE
 FOLLOWING IS A LIST OF THE FIXTURE
 LAYOUT CHANGES THAT NEED TO BE REFLECTED
 ON THE SANITARY ISOMETRIC RISER DIAGRAM
 IN ORDER TO PASS PLUMBING PLAN REVIEW.
 A) KITCHEN SINK RELOCATED
 B) WASHING MACHINE RELOCATED
 C) 1 (ONE) LAVATORY DELETED
 D) SHOWER RELOCATED
 E) 1 (ONE) WATER CLOSET OR BIDET ADDED
 IN SHOWER BATH, PLEASE IDENTIFY THAT
 ADDED FIXTURE
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  