Plan Review Notes
Plan Review Notes For Permit 06040846
Permit Number 06040846
Review Stop P
Sequence Number 2
Notes
Date Text
2006-06-13 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING IS STILL REQUIRED FOR
 PLUMBING PLAN REVIEW:
  
 1. PLEASE INDICATE ALL PIPE SIZES ON
 ISOMETRIC PLUMBING RISER DIAGRAM PER
 FBC-2004 CHAPTER 1 SECTION 106.3.5.4
 PLEASE SEE CORRECTED DRAWING IN RED INK
 ON SHEET A-3.
 2. THE WASHING MACHINE INDICATED ON
 SHEET A-3 IS STILL NOT SIZED PROPERLY
 PER THE FOLLOWING.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. (NOTE: PLEASE SEE CORRECTED
 DRAWING ON SHEET A-3 FOR REFERENCE FOR
 RESUBMITTAL)
 3. PLEASE SEE ON THE CORRECTED DRAWING
 SHEET A-3 THE CLEANOUT LOCATIONS PER THE
 FOLLOWING.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (NOTE: PLEASE CORRECT THE POSITION OF
 THE TWO WAY CLEANOUT ON SHEET A-3, SEE
 SHEET A-3 CORRECTED DRAWING FOR
 REFERENCE FOR RESUBMITTAL)
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)(NOTE:
 THE CLEANOUT SIZE 3" OF THE WASHING
 MACHINE)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. (NOTE: THE
 LOCATION OF THE WASHING MACHINE CLEANOUT
 SHALL BE LOCATED 4' ABOVE FINNISH FLOOR)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  