Plan Review Notes For Permit 06040846 |
Permit Number |
06040846 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-02 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 PLUMBING | | | | PLEASE ADJUST YOUR DRAWINGS TO REFLECT | | THE FOLLOWING CHANGES REQUIRED FOR PLAN | | REVIEW: NOTE, ONLY ONE DRAWING INDICATES | | PLUMBING CORRECTIONS: | | | | 1. THE SHOWER INDICATED ON THE ISOMETRIC | | DRAINAGE RISER DIAGRAM ON SHEET A-3 IS | | NOT VENTED PER 909.1 WET VENTS, PLEASE | | SEE CORRECTED DRAWING AND ADJUST | | DRAWINGS FOR RESUBMITTAL. | | 2. THE WASHING MACHINE INDICATED ON THE | | ISOMETRIC DRAINAGE RISER DIAGRAM IS NOT | | SIZED PER 406.3, BRANCH DRAIN OR | | DRAINAGE STACK MINIMUM 3". PER 708.7 | | CLEANOUTS SHALL BE THE SAME NOMINAL SIZE | | AS THE PIPE THEY SERVE UP TO 4". PER | | 708.9 ACCESS SHALL BE PROVIDED TO ALL | | CLEANOUTS. PLEASE SEE CORRECTED DRAWING | | AND ADJUST DRAWINGS FOR RESUBMITTAL. | | 3. PLEASE INDICATE THE WASHING MACHINE, | | DRYER, AND WATER HEATER ON THE PROPOSED | | FLOOR PLAN. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K/STEVENS | | (561) 805-6721 |
|