2006-06-13 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING IS STILL REQUIRED FOR
 PLUMBING PLAN REVIEW:
  
 1.THERE HAS BEEN NO ATTEMPT TO CORRECT
 THE ISOMETRIC PLUMBING RISER DIAGRAM ON
 SHEET 3/3, UNTIL THESE CHANGES HAVE BEEN
 MET PERMIT CAN NOT BE ISSUED.
 2. CHANGE UNDER SINK VENT TO READ AIR
 ADMITTANCE VALVE PER FBC-2004 PLUMBING
 SECTION 917, SEE CORRECTED DRAWING ON
 SHEET 3/3 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 3. PER CHAPTER 1, SECTION 106.1.1: THE
 SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. SHEET 3/3
 FLOOR PLAN INDICATES TWO 2" PVC UNDER
 SINK VENTS WHICH SHOULD BE INDICATED AS
 AIR ADMITTANCE VALVES (A.A.V.) AND RISER
 DIAGRAM INDICATES ONE AIR ADMITTANCE
 VALVE (A.A.V.) PLEASE CORRELATE DRAWING
 FOR RESUBMITTAL.
 4.CLEANOUTS ARE REQUIRED AT THE BASE OF
 WASTE STACKS AND NEAR THE JUNCTION OF
 THE BUILDING DRAIN AND THE BUILDING
 SEWER, PER FBC-2004 PLUMBING, SECTION
 708.3.4 AND SECTION 708.3.5. THE
 ISOMETRIC PLUMBING RISER DIAGRAM NEEDS
 TO INDICATE THE CLEANOUTS, PLEASE SEE
 CORRECTED DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL.
 5.NOTE: A PLUMBING PERMIT WILL BE
 REQUIRED FOR THE PLUMBING WORK INDICATED
 ON DRAWINGS, PLUMBING CONTRACTOR SHALL
 REFERENCE PERMIT #06040807 WHEN PLUMBING
 PERMIT IS APPLIED FOR.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721