2006-06-13 00:00:00 | ******DENIED 2ND TIME****** |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING IS STILL REQUIRED FOR |
| PLUMBING PLAN REVIEW: |
| |
| 1.THERE HAS BEEN NO ATTEMPT TO CORRECT |
| THE ISOMETRIC PLUMBING RISER DIAGRAM ON |
| SHEET 3/3, UNTIL THESE CHANGES HAVE BEEN |
| MET PERMIT CAN NOT BE ISSUED. |
| 2. CHANGE UNDER SINK VENT TO READ AIR |
| ADMITTANCE VALVE PER FBC-2004 PLUMBING |
| SECTION 917, SEE CORRECTED DRAWING ON |
| SHEET 3/3 IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| 3. PER CHAPTER 1, SECTION 106.1.1: THE |
| SANITARY ISOMETRIC RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN. SHEET 3/3 |
| FLOOR PLAN INDICATES TWO 2" PVC UNDER |
| SINK VENTS WHICH SHOULD BE INDICATED AS |
| AIR ADMITTANCE VALVES (A.A.V.) AND RISER |
| DIAGRAM INDICATES ONE AIR ADMITTANCE |
| VALVE (A.A.V.) PLEASE CORRELATE DRAWING |
| FOR RESUBMITTAL. |
| 4.CLEANOUTS ARE REQUIRED AT THE BASE OF |
| WASTE STACKS AND NEAR THE JUNCTION OF |
| THE BUILDING DRAIN AND THE BUILDING |
| SEWER, PER FBC-2004 PLUMBING, SECTION |
| 708.3.4 AND SECTION 708.3.5. THE |
| ISOMETRIC PLUMBING RISER DIAGRAM NEEDS |
| TO INDICATE THE CLEANOUTS, PLEASE SEE |
| CORRECTED DRAWING IN RED INK FOR |
| REFERENCE FOR RESUBMITTAL. |
| 5.NOTE: A PLUMBING PERMIT WILL BE |
| REQUIRED FOR THE PLUMBING WORK INDICATED |
| ON DRAWINGS, PLUMBING CONTRACTOR SHALL |
| REFERENCE PERMIT #06040807 WHEN PLUMBING |
| PERMIT IS APPLIED FOR. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| |
| END OF COMMENTS: |
| |