Plan Review Notes
Plan Review Notes For Permit 06040702
Permit Number 06040702
Review Stop P
Sequence Number 2
Notes
Date Text
2006-07-10 00:00:00DENIED;
 1.(NOT ADDRESSED) OLD NOT 1.WATER HAMMER
 ARRESTORSTO BE USED PER. FBC-2004
 PLUMBING SEC. 604.9, AND ARE TO BE
 INSTALLED PER MANUFACTURE'S
 SPECIFICATIONS, AS CLOSE TO THE SORCE OF
 HAMMER AS POSSIBLE.
 2.(OLD NOTE #3) PLUMBING FIXTURE
 SCHEDULE WAS CHANGED TO REFERENCE HIGH
 LOW DRINKING FOUNTAIN BUT DRAWINGS OF
 DRINKING FOUNTAIN AND RISER DIAGRAM
 STILL SHOW SINGLE FOUNTAIN. A NOTE WILL
 WORK "HI-LOW DRINKING FOUNTAIN" ON PAGE
 1 AND 6.
 3.WATER RISER DIAGRAM IS MISSING
 STUBOUTS FOR 4 TOILETS AND TWO LAVS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695