Plan Review Notes For Permit 06040702 |
Permit Number |
06040702 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-07-10 00:00:00 | DENIED; | | 1.(NOT ADDRESSED) OLD NOT 1.WATER HAMMER | | ARRESTORSTO BE USED PER. FBC-2004 | | PLUMBING SEC. 604.9, AND ARE TO BE | | INSTALLED PER MANUFACTURE'S | | SPECIFICATIONS, AS CLOSE TO THE SORCE OF | | HAMMER AS POSSIBLE. | | 2.(OLD NOTE #3) PLUMBING FIXTURE | | SCHEDULE WAS CHANGED TO REFERENCE HIGH | | LOW DRINKING FOUNTAIN BUT DRAWINGS OF | | DRINKING FOUNTAIN AND RISER DIAGRAM | | STILL SHOW SINGLE FOUNTAIN. A NOTE WILL | | WORK "HI-LOW DRINKING FOUNTAIN" ON PAGE | | 1 AND 6. | | 3.WATER RISER DIAGRAM IS MISSING | | STUBOUTS FOR 4 TOILETS AND TWO LAVS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|