2006-07-12 00:00:00 | |
| |
| |
| DENIED |
| |
| PREVIOUS NOTES NOT ADDRESSED: |
| |
| 6) PRODUCT APPROVAL FOR BUILT UP ROOFING |
| DOES NOT ALLOW FOR ENHANCED FASTENING IN |
| THE PERIMETER AND CORNER ZONES (SEE |
| LIMITATION #9) AS SUCH THIS PRODUCT WILL |
| NOT BE ACCEPTABLE (NOT ADDRESSED) |
| |
| 7) NOTE #5, SHT.1 STATES REPLACEMENT OF |
| DOORS,FRAMES AND HARDWARE. PLEASE MARK |
| NOA'S WITH DOOR TYPE USED, FRAME |
| ATTACHMENT METHOD AND PROVIDE HARDWARE |
| SCHEDULE (NOTE 5 STATES AL SERIES, |
| PRODUCT APPROVAL D18 & E18) CLARIFY |
| |
| 9) NOTE #17, SHT.1 HC STALL WILL NOT |
| MEET THE REQUIREMENTS FOR CLEAR FLOOR |
| SPACE, LAVATORY ENCROACHES ON THE |
| REQUIRED FLOOR SPACE FOR THE WATER |
| CLOSET (SEE FIG. 30E IN CHAPTER 11 FBC) |
| ( WILL NOT MEET FIXTURE COUNT, PROVIDE |
| OCCUPANT LOAD FOR AREA) |
| |
| 10) THOSE PRODUCTS WHICH ARE REGULATED |
| BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| ( NEEDS APPROVAL OF DESIGNER OF RECORD) |
| *************************************** |
| |
| 1) NOTE #9 SPECIFIES PGT WINDOWS NOT |
| SHUTTERS AS SUBMITTED PRODUCT APPROVALS |
| |
| 2) NOTE #11 RECONDITIONING OF OLD |
| SHUTTER OR NEW ? |
| |
| 3) SHUTTER NOA DOES NOT HAVE ATTACHMENT |
| METHOD TO WOOD FRAMING, ONLY CONCRETE |
| ATTACHMENT IS CONSIDERED |
| |
| 4) PROVIDE EXISTING FLOOR PLAN LAYOUT |
| |
| |
| |
| NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| FBC* = WEST PALM BEACH |
| ADMINISTATIVE AMMENDMENTS TO FBC |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |