Plan Review Notes
Plan Review Notes For Permit 06040702
Permit Number 06040702
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-12 00:00:00 
  
  
 DENIED
  
 PREVIOUS NOTES NOT ADDRESSED:
  
 6) PRODUCT APPROVAL FOR BUILT UP ROOFING
 DOES NOT ALLOW FOR ENHANCED FASTENING IN
 THE PERIMETER AND CORNER ZONES (SEE
 LIMITATION #9) AS SUCH THIS PRODUCT WILL
 NOT BE ACCEPTABLE (NOT ADDRESSED)
  
 7) NOTE #5, SHT.1 STATES REPLACEMENT OF
 DOORS,FRAMES AND HARDWARE. PLEASE MARK
 NOA'S WITH DOOR TYPE USED, FRAME
 ATTACHMENT METHOD AND PROVIDE HARDWARE
 SCHEDULE (NOTE 5 STATES AL SERIES,
 PRODUCT APPROVAL D18 & E18) CLARIFY
  
 9) NOTE #17, SHT.1 HC STALL WILL NOT
 MEET THE REQUIREMENTS FOR CLEAR FLOOR
 SPACE, LAVATORY ENCROACHES ON THE
 REQUIRED FLOOR SPACE FOR THE WATER
 CLOSET (SEE FIG. 30E IN CHAPTER 11 FBC)
 ( WILL NOT MEET FIXTURE COUNT, PROVIDE
 OCCUPANT LOAD FOR AREA)
  
 10) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 ( NEEDS APPROVAL OF DESIGNER OF RECORD)
 ***************************************
  
 1) NOTE #9 SPECIFIES PGT WINDOWS NOT
 SHUTTERS AS SUBMITTED PRODUCT APPROVALS
  
 2) NOTE #11 RECONDITIONING OF OLD
 SHUTTER OR NEW ?
  
 3) SHUTTER NOA DOES NOT HAVE ATTACHMENT
 METHOD TO WOOD FRAMING, ONLY CONCRETE
 ATTACHMENT IS CONSIDERED
  
 4) PROVIDE EXISTING FLOOR PLAN LAYOUT
  
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  