Plan Review Notes For Permit 06040702 |
Permit Number |
06040702 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-24 00:00:00 | DENIED; | | 1.WATER HAMMER ARRESTORS TO BE USED PER. | | FBC-2004 PLUMBING SEC. 604.9, AND TO BE | | INSTALLED PER MANUFACTURE'S | | SPECIFICATIONS, AS CLOSE TO THE SOURCE | | OF HAMMER AS POSSIBLE. | | 2.WATER RISER DIAGRAM NOTE "A" (ADD TO | | NOTE), PROTECTIVE COATING REQUIRED TO | | PROTECT COPPER FROM CORROSION. | | 3.DRINKING FOUNTAIN TO COMPLY WITH | | FBC-2004 CHAPTER 11 SEC. 11-4.1.3(10(A. | | HIGH LOW FOUNTAIN REQUIRED . | | 4.SHOW DETAIL OF FIXTURES IN HANDICAP | | STALLS @TOILET 18" OFF WALL, FIG. 28 AND | | LAVATORY TO BE 5" OFF WALL, FIG. 32. | | FLUSH VALVES PER SEC. 416.5. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|