Notes
Date Text
2006-04-24 00:00:00DENIED;
 1.WATER HAMMER ARRESTORS TO BE USED PER.
 FBC-2004 PLUMBING SEC. 604.9, AND TO BE
 INSTALLED PER MANUFACTURE'S
 SPECIFICATIONS, AS CLOSE TO THE SOURCE
 OF HAMMER AS POSSIBLE.
 2.WATER RISER DIAGRAM NOTE "A" (ADD TO
 NOTE), PROTECTIVE COATING REQUIRED TO
 PROTECT COPPER FROM CORROSION.
 3.DRINKING FOUNTAIN TO COMPLY WITH
 FBC-2004 CHAPTER 11 SEC. 11-4.1.3(10(A.
 HIGH LOW FOUNTAIN REQUIRED .
 4.SHOW DETAIL OF FIXTURES IN HANDICAP
 STALLS @TOILET 18" OFF WALL, FIG. 28 AND
 LAVATORY TO BE 5" OFF WALL, FIG. 32.
 FLUSH VALVES PER SEC. 416.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695