Plan Review Notes For Permit 06040702
Permit Number 06040702
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE #4 CU PER 250.66 FOR 3/0 SERVICE
 ENTRANCE CONDUCTORS.
  
 2} THE CONTINUOUS LOADS IN THE PANEL
 SCHEDULE MUST BE CALCULATED @ 125% PER
 210.20(A).
  
 3} PLEASE COMPLETE THE INFORMATION IN
 THE PANEL SPECIFICATION SECTION.
  
 IF THERE AER ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/805-6731