2006-05-09 00:00:00 | |
| |
| DENIED |
| |
| 1) PROVIDE WIND DESIGN CRITERIA PER |
| 1603.1.4 FBC. SHOW COMPONENT AND |
| CLADDING DESIGN PRESSURES TO DOORS AND |
| WINDOWS |
| |
| 2) PROVIDE FRAMING DETAILS THAT SHOW |
| ATTACHMENT/STRAPPING OF NEW DOUBLE 2X12 |
| HEADERS AND SILLS ETC. ON PRESSBOX |
| |
| 3) PROVIDE PLAN VIEW OF PRESSBOX SHOWING |
| WINDOW LAYOUT, GIVE SIZES AND AMOUNT OF |
| WINDOWS, WILL THEY BE FRAMED |
| INDIVIDUALLY OR USE PGT MULLIONS. |
| |
| 4) NO PRODUCT APPROVALS WERE SUBMITTED |
| FOR WINDOWS OR MULLIONS IF USED. |
| |
| 5) PRODUCT APPROVAL FOR ROLL UP DOOR WAS |
| SUBMITTED, WHERE IS THIS PRODUCT BEING |
| USED? IT IS NOT ON DRAWINGS. ALSO IF |
| PRODUCT IS TO BE INCORPORATED INTO |
| DRAWING NEW UPDATED NOA WILL BE REQUIRED |
| AS THIS ONE HAS EXPIRED |
| |
| 6) PRODUCT APPROVAL FOR BUILT UP ROOFING |
| DOES NOT ALLOW FOR ENHANCED FASTENING IN |
| THE PERIMETER AND CORNER ZONES (SEE |
| LIMITATION #9) AS SUCH THIS PRODUCT WILL |
| NOT BE ACCEPTABLE |
| |
| 7) NOTE #5, SHT.1 STATES REPLACEMENT OF |
| DOORS,FRAMES AND HARDWARE. PLEASE MARK |
| NOA'S WITH DOOR TYPE USED, FRAME |
| ATTACHMENT METHOD AND PROVIDE HARDWARE |
| SCHEDULE |
| |
| 8) NOTE #6, SHT.1 STATES REPLACEMENT OF |
| TOILET PARTIONS WITH PLASTIC MATERIAL |
| BUT DRAWING SHOWS U-BLOCK WALLS WITH HCM |
| DOOR AS IN NOTE #5 PLEASE CLARIFY |
| |
| 9) NOTE #17, SHT.1 HC STALL WILL NOT |
| MEET THE REQUIREMENTS FOR CLEAR FLOOR |
| SPACE, LAVATORY ENCROACHES ON THE |
| REQUIRED FLOOR SPACE FOR THE WATER |
| CLOSET (SEE FIG. 30E IN CHAPTER 11 FBC) |
| |
| 10) THOSE PRODUCTS WHICH ARE REGULATED |
| BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| |
| 11) CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION,NATURE, AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| PER 106.1.1 FBC* (PROVIED LEGIBLE NOA'S |
| THESE MUST BE READABLE FOR FIELD |
| INSPECTIONS) |
| |
| NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| FBC* = WEST PALM BEACH |
| ADMINISTATIVE AMMENDMENTS TO FBC |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| BLDG PLAN REVIEW |