2006-08-04 00:00:00 | ****** UNSAT2ND REVIEW ******** |
| |
| ** PLEASE SEE SOME OF THE NOTES FROM |
| PREVIOUS REVIEW STILL NEED TO BE |
| ADDRESSED. |
| PLEASE ALSO SEE NEW COMMENT FOR HAND |
| WRITTEN ITEMS ON PLANS. |
| |
| 1) NOTE:NO , PLEASE SEE ALL OLD/VOIDED |
| SHEETS WERE LEFT IN SETS WHEN REQUESTED |
| TO BE REMOVED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE BE SURE TO COMPLETELY |
| REMOVED ANY OF THE OLD/VOIDED SHEETS |
| FROM SETS AND ONLY INSERT THE NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| THIS WILL HELP TO AVOID ANY DELAYS IN |
| PROCESSING PROJECT. |
| ** ONE COPY OF ANY OLD/VOIDED REMOVED |
| SHEETS SHOULD BE SUBMITTED SEPARATELY |
| FOR REFERENCE. |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE:NO, NOTE MENTIONS ALL ADOPTED |
| CODES, HOWEVER PLEASE SEE THAT THE CODES |
| RELEVANT TO DESIGN SHALL BE SPECIFIC AND |
| ON PLANS.PLEASE SEE MIN CODES WHICH WERE |
| GIVEN BELOW TO BE STATED ON ELECTRICAL |
| PLANS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE PLANS SHALL |
| REFERENCE THE CURRENT CODES IN EFFECT. |
| PLEASE SEE PLANS NOW INDICATE THE |
| "LATEST CODES". WE ARE NOT CURRENTLY |
| UNDER THE LATEST CODES AS THEY HAVE NOT |
| YET BEEN ADOPTED BY THE STATE OF |
| FLORIDA. |
| PLEASE SEE THE FOLLOWING AT A MIN SHOULD |
| BEON PLANS. 2002 NFPA-70, 2003 NFPA-101, |
| 2002 NFPA-72. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE: OK. SEE NEW NOTES. |
| |
| 8) NOTE: NO? PLEASE SEE LOAD |
| CALCULATIONS MENTIONS A LOAD FOR PANEL |
| "C" HOWEVER HOW AND WHERE ARE LOADS |
| DERIVED. PLEASE SEE AS NOTED ON PREVIOUS |
| NOTE, PLEASE INDICATE THE LOADS(DRYER, |
| WASHER, SM APPLIANCE CIRCUITS, ETC |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE LOAD CALCULATIONS |
| SHALL INCLUDE ALL LOADS ON EXISTING |
| PANEL "C" AS THIS EXISTING PANEL "C" IS |
| BEING FED FROM NEW 225A MAIN, YET LOAD |
| CALCULATIONS ON SHOW NEW HOUSE PANEL |
| LOADS. |
| 215.5,220.31B. UNABLE TO VERIFY MANY |
| ITEMS FROM EXISTING PANEL AND LOADS AT |
| THIS TIME. PLEASE SEE NEC FOR MIN LOADS |
| REQUIRED FOR DRYER AND WASHER/LAUNDRY. |
| 220.18, 220.16 ETC. |
| |
| 9) NOTE: NO, PLEASE SEE ROOM WHICH IS |
| BEING IDENTIFIED AT "PANTRY" A RECEPT |
| WAS REDLINED FOR WALL SPACE AS THIS IS |
| BEING SHOWN AS A ROOM. IF THIS IS A |
| "HALL" THEN ADJUST ACCORDINGLY. |
| PLEASE SEE BEDRM UPSTAIRS AS PREVIOUS |
| PLANS WERE REDLINED FOR MORE THAN 2' OF |
| WALL IN BEDRM #1 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEEPLEASE SEE MISSING RECEPTS |
| PER |
| 210.52 |
| |
| 10) NOTE:NO, PLEASE SEE PREVIOUS PLANS |
| WERE REDLINE WHERE THIS WOULD BE |
| REQUIRED. PLEASE SEE COUNTER IS OVER 8' |
| WHICH WOULD REQUIRE 3 COUNTER SPACE |
| RECEPTS. |
| PLEASE SEE THE THIRD RECEPT SHOWN IS FOR |
| THE DISPOSAL. |
| PLEASE SEE PLANS ARE REDLINED ONCE AGAIN |
| AT THAT LOCATION. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING GFI RECEPT |
| ALONG KITCHEN COUNTER SPACE PER |
| 210.52C1,210.8A6. |
| |
| 11) NOTE:OK/NO, WATER HEATER IS NOW |
| BEING SHOWN W/ 2500W HEAT, HOWEVER CAN |
| NOT VERIFY THE LOAD AS THIS IS NOT |
| PLACED IN LOAD CALCULATIONS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CLARIFY WATER HEATER, |
| NEW , EXISTING ETC. NOWATER HEATER IS |
| SHOWN ON ELECTRICAL PLANS. THIS IS SHOWN |
| ON "P" SHEETS, HOWEVER THE LOAD SHALL |
| ALSO BE INCLUDED WITH LOAD CALCULATIONS |
| FOR SERVICE. |
| 215.5, 220.31B |
| |
| 12) NOTE: OK. |
| |
| 13) NOTE: OK. |
| |
| 14) NOTE: OK. |
| |
| 15) NOTE: OK. |
| |
| 16)NOTE:NO, ONLY SHOWN FOR PANELS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 17) NOTE: NO, THIS IS THE SAME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE RISER IS SHOWING |
| "EQUIPMENT GROUNDING CONDUCTORS" FROM |
| METER TO MAINS. PLEASE SEE THE EQP GRNDS |
| ARE ONLY INSTALLED AFTER THE FIRST MEANS |
| OF DISCONNECT. |
| 250.6,250.24B |
| |
| 18) NOTE: OK. |
| |
| 19) NOTE: STILL SHOWING THE FOOTER STEEL |
| AT EXISTING GUEST HOUSE? THIS IS OK. |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE SEE GROUNDING ELECTRODE |
| RISER AT GUEST HOUSE WHICH INDICATES |
| FOOTER STEEL? PLEASE KNOW, AS AN |
| EXSITING BUILDING, THIS IS NOT REQUIRED |
| AT GUEST HOUSE , ONLY MAIN HOUSE. PLEASE |
| KNOW, THE STRUCTURAL INTEGRITY OF THE |
| EXISTING FOOTER MAY BE COMPOMISED TO |
| ATTACH. PLEASE KNOW, GIVEN THE AGE OF |
| THE EXISTING FOOTER IN THIS GUEST HOUSE, |
| FOOTER STEEL MAY NOT BE PRESENT AT |
| ALL.?? |
| THIS IS FOR INFORMATION ONLY AS, IT MAY |
| BE DONE, BUT NOT REQUIRED AT GUEST |
| HOUSE. |
| |
| 20) NOTE:NO, PLEASE SEE A NOTE WAS |
| ADDED TO ONLY ONE. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SEE DISCONNECT AND AHU |
| IN CLOSETS SEEMS TO BE LOCATED |
| NOT TO MEET 110.26 AND THE MECHANICAL |
| CODE. |
| PLEASE ALSO SEE 240.24D AS OCP IS NOT |
| PERMITTED IN A CLOTHES/STORAGE CLOSET. |
| PLEASE SEE THIS LOCATION AND THE CLOSE |
| PROXIMITY TO EASILY IGNITIBLE MATERIALS. |
| |
| 21) NOTE: OK. |
| |
| 22) NOTE: OK. |
| |
| 23) NOTE:NO, PLEASE SEE OCP ON SOME |
| UNITS ON PANEL SCHEDULE EXCEED THE MAX |
| OCP RATING AS STATED ON MECH PLANS> |
| PLEASE ADJUST AND CORRELATE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRLELATE ALL A/C |
| SYSTEMS, OCP AND LOADS, AS THESE SHOWN |
| ON ELECTRICAL PANEL SCHEDULE DO NOT |
| MATCH WITH THOSE AS SHOWN ON MECH |
| SHEETS. |
| |
| 24) NOTE:SAME, IF SHOWN THIS WAY OK, |
| HOWEVER SIZE WILL BE REQUIRED TO BE |
| REVISED. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE VERIFY THE SIZE OF THE |
| NEW METER CAN BEING SHOWN AS 225A?? THIS |
| IS NOT KNOWN AS A COMMON SIZE. PLEASE |
| ADJUST. |
| 215.5 |
| |
| **** NEW NOTES **** |
| |
| 25) NOTE: PLEASE SEE NO HAND WRITTEN |
| CHANGES CAN BE MADE TO PLANS WHICH ARE |
| SIGNED , DATED AND SEALED BY THE |
| ENGINEER. IF ANY CHANGES ARE MADE BY |
| HAND, EACH AND EVERY ITEM SHALL CONTAIN |
| INITIALS OF SAID DESIGNER AND DATE. |
| FS 471.025, FAC 61G15-23.002 |
| |
| 26) NOTE: PLEASE SEE NOTICE GIVEN FOR |
| FS553.80(2)9B). |
| THIS IS ONLY A NOTICE. |
| |
| ** PLEASE KNOW,MANY OF THE ABOVE ITEMS |
| ARE REDLINED ON ONE OF THE SETS OF |
| PLANS, HOWEVER IS IN NO WAY ALL |
| LOCATIONS AS NOTED ABOVE. |
| |
| ** PLEASE SUBMIT THE ABOVE FOR REVIEW |
| AND IF THERE ARE ANY QUESTIONS OR |
| COMMENTS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |