Plan Review Notes
Plan Review Notes For Permit 06040626
Permit Number 06040626
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-04 00:00:00****** UNSAT2ND REVIEW ********
  
 ** PLEASE SEE SOME OF THE NOTES FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
 PLEASE ALSO SEE NEW COMMENT FOR HAND
 WRITTEN ITEMS ON PLANS.
  
 1) NOTE:NO , PLEASE SEE ALL OLD/VOIDED
 SHEETS WERE LEFT IN SETS WHEN REQUESTED
 TO BE REMOVED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO COMPLETELY
 REMOVED ANY OF THE OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 THIS WILL HELP TO AVOID ANY DELAYS IN
 PROCESSING PROJECT.
 ** ONE COPY OF ANY OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED SEPARATELY
 FOR REFERENCE.
  
 2) NOTE: OK.
  
 3) NOTE:NO, NOTE MENTIONS ALL ADOPTED
 CODES, HOWEVER PLEASE SEE THAT THE CODES
 RELEVANT TO DESIGN SHALL BE SPECIFIC AND
 ON PLANS.PLEASE SEE MIN CODES WHICH WERE
 GIVEN BELOW TO BE STATED ON ELECTRICAL
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODES IN EFFECT.
 PLEASE SEE PLANS NOW INDICATE THE
 "LATEST CODES". WE ARE NOT CURRENTLY
 UNDER THE LATEST CODES AS THEY HAVE NOT
 YET BEEN ADOPTED BY THE STATE OF
 FLORIDA.
 PLEASE SEE THE FOLLOWING AT A MIN SHOULD
 BEON PLANS. 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK. SEE NEW NOTES.
  
 8) NOTE: NO? PLEASE SEE LOAD
 CALCULATIONS MENTIONS A LOAD FOR PANEL
 "C" HOWEVER HOW AND WHERE ARE LOADS
 DERIVED. PLEASE SEE AS NOTED ON PREVIOUS
 NOTE, PLEASE INDICATE THE LOADS(DRYER,
 WASHER, SM APPLIANCE CIRCUITS, ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LOAD CALCULATIONS
 SHALL INCLUDE ALL LOADS ON EXISTING
 PANEL "C" AS THIS EXISTING PANEL "C" IS
 BEING FED FROM NEW 225A MAIN, YET LOAD
 CALCULATIONS ON SHOW NEW HOUSE PANEL
 LOADS.
 215.5,220.31B. UNABLE TO VERIFY MANY
 ITEMS FROM EXISTING PANEL AND LOADS AT
 THIS TIME. PLEASE SEE NEC FOR MIN LOADS
 REQUIRED FOR DRYER AND WASHER/LAUNDRY.
 220.18, 220.16 ETC.
  
 9) NOTE: NO, PLEASE SEE ROOM WHICH IS
 BEING IDENTIFIED AT "PANTRY" A RECEPT
 WAS REDLINED FOR WALL SPACE AS THIS IS
 BEING SHOWN AS A ROOM. IF THIS IS A
 "HALL" THEN ADJUST ACCORDINGLY.
 PLEASE SEE BEDRM UPSTAIRS AS PREVIOUS
 PLANS WERE REDLINED FOR MORE THAN 2' OF
 WALL IN BEDRM #1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEEPLEASE SEE MISSING RECEPTS
 PER
 210.52
  
 10) NOTE:NO, PLEASE SEE PREVIOUS PLANS
 WERE REDLINE WHERE THIS WOULD BE
 REQUIRED. PLEASE SEE COUNTER IS OVER 8'
 WHICH WOULD REQUIRE 3 COUNTER SPACE
 RECEPTS.
 PLEASE SEE THE THIRD RECEPT SHOWN IS FOR
 THE DISPOSAL.
 PLEASE SEE PLANS ARE REDLINED ONCE AGAIN
 AT THAT LOCATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING GFI RECEPT
 ALONG KITCHEN COUNTER SPACE PER
 210.52C1,210.8A6.
  
 11) NOTE:OK/NO, WATER HEATER IS NOW
 BEING SHOWN W/ 2500W HEAT, HOWEVER CAN
 NOT VERIFY THE LOAD AS THIS IS NOT
 PLACED IN LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY WATER HEATER,
 NEW , EXISTING ETC. NOWATER HEATER IS
 SHOWN ON ELECTRICAL PLANS. THIS IS SHOWN
 ON "P" SHEETS, HOWEVER THE LOAD SHALL
 ALSO BE INCLUDED WITH LOAD CALCULATIONS
 FOR SERVICE.
 215.5, 220.31B
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: OK.
  
 15) NOTE: OK.
  
 16)NOTE:NO, ONLY SHOWN FOR PANELS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 17) NOTE: NO, THIS IS THE SAME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER IS SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 METER TO MAINS. PLEASE SEE THE EQP GRNDS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
 250.6,250.24B
  
 18) NOTE: OK.
  
 19) NOTE: STILL SHOWING THE FOOTER STEEL
 AT EXISTING GUEST HOUSE? THIS IS OK.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE GROUNDING ELECTRODE
 RISER AT GUEST HOUSE WHICH INDICATES
 FOOTER STEEL? PLEASE KNOW, AS AN
 EXSITING BUILDING, THIS IS NOT REQUIRED
 AT GUEST HOUSE , ONLY MAIN HOUSE. PLEASE
 KNOW, THE STRUCTURAL INTEGRITY OF THE
 EXISTING FOOTER MAY BE COMPOMISED TO
 ATTACH. PLEASE KNOW, GIVEN THE AGE OF
 THE EXISTING FOOTER IN THIS GUEST HOUSE,
 FOOTER STEEL MAY NOT BE PRESENT AT
 ALL.??
 THIS IS FOR INFORMATION ONLY AS, IT MAY
 BE DONE, BUT NOT REQUIRED AT GUEST
 HOUSE.
  
 20) NOTE:NO, PLEASE SEE A NOTE WAS
 ADDED TO ONLY ONE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE DISCONNECT AND AHU
 IN CLOSETS SEEMS TO BE LOCATED
 NOT TO MEET 110.26 AND THE MECHANICAL
 CODE.
 PLEASE ALSO SEE 240.24D AS OCP IS NOT
 PERMITTED IN A CLOTHES/STORAGE CLOSET.
 PLEASE SEE THIS LOCATION AND THE CLOSE
 PROXIMITY TO EASILY IGNITIBLE MATERIALS.
  
 21) NOTE: OK.
  
 22) NOTE: OK.
  
 23) NOTE:NO, PLEASE SEE OCP ON SOME
 UNITS ON PANEL SCHEDULE EXCEED THE MAX
 OCP RATING AS STATED ON MECH PLANS>
 PLEASE ADJUST AND CORRELATE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRLELATE ALL A/C
 SYSTEMS, OCP AND LOADS, AS THESE SHOWN
 ON ELECTRICAL PANEL SCHEDULE DO NOT
 MATCH WITH THOSE AS SHOWN ON MECH
 SHEETS.
  
 24) NOTE:SAME, IF SHOWN THIS WAY OK,
 HOWEVER SIZE WILL BE REQUIRED TO BE
 REVISED.
  
 ** PREVIOUS NOTE **
 PLEASE VERIFY THE SIZE OF THE
 NEW METER CAN BEING SHOWN AS 225A?? THIS
 IS NOT KNOWN AS A COMMON SIZE. PLEASE
 ADJUST.
 215.5
  
 **** NEW NOTES ****
  
 25) NOTE: PLEASE SEE NO HAND WRITTEN
 CHANGES CAN BE MADE TO PLANS WHICH ARE
 SIGNED , DATED AND SEALED BY THE
 ENGINEER. IF ANY CHANGES ARE MADE BY
 HAND, EACH AND EVERY ITEM SHALL CONTAIN
 INITIALS OF SAID DESIGNER AND DATE.
 FS 471.025, FAC 61G15-23.002
  
 26) NOTE: PLEASE SEE NOTICE GIVEN FOR
 FS553.80(2)9B).
 THIS IS ONLY A NOTICE.
  
 ** PLEASE KNOW,MANY OF THE ABOVE ITEMS
 ARE REDLINED ON ONE OF THE SETS OF
 PLANS, HOWEVER IS IN NO WAY ALL
 LOCATIONS AS NOTED ABOVE.
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW
 AND IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  