Plan Review Notes
Plan Review Notes For Permit 06040626
Permit Number 06040626
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-25 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE BE SURE TO COMPLETELY
 REMOVED ANY OF THE OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 THIS WILL HELP TO AVOID ANY DELAYS IN
 PROCESSING PROJECT.
 ** ONE COPY OF ANY OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED SEPARATELY
 FOR REFERENCE.
  
 2) NOTE: PLEASE SEE CIRCUITING FOR BATH
 RECEPT ON FIRST FLR IS CIRCUITED TO
 ELEVATOR LTS. PLEASE SEE
 210.52D,210.11C3. BATH(S) REQUIRE
 DEDICATED CIRCUITS AS SET FORTH IN CODES
 REF.
  
 3) NOTE: PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODES IN EFFECT.
 PLEASE SEE PLANS NOW INDICATE THE
 "LATEST CODES". WE ARE NOT CURRENTLY
 UNDER THE LATEST CODES AS THEY HAVE NOT
 YET BEEN ADOPTED BY THE STATE OF
 FLORIDA.
 PLEASE SEE THE FOLLOWING AT A MIN SHOULD
 BEON PLANS. 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72.
  
 4) NOTE: PLEASE SEE THE DISCONNECTING
 MEANS AT MAIN HOUSE SHOULD BE LOCATED AT
 THE NEAREST POINT OF ENTRANCE TO THE
 DWELLING. 225.31-225.34
  
 5) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROLS IN MANY LOCATIONS.
 PLEASE SEE ALL RMS IN HOUSE WHICH
 INDICATE A SW FOR A FAN AND A
 FAN J-BOX ONLY??
 PLEASE KNOW, A LT FIXTURE WILL BE
 REQUIRED OR 1/2 SWITCHED RECEPT.
 PLEASE SEE OTHER LOCATIONS IN MAIN HOUSE
 FOR LOCATIONS OF MEANS OF EGRESS AND
 WHERE A LT FIXTURE OF SOME SORT WILL BE
 REQUIRED.
 PLEASE SEE KITCHEN EGRESS FROM
 BREAKFAST/PANTRY AREAS?
 210.70, LS 101 7.8, RESIDENTIAL CHAPTER
 24.
  
 6) NOTE: PLEASE SEE SD'S ARE NOTALL
 SHOWN WITH CIRCUITING? PLEASE SEE ONE SD
 IS CIRCUITED HOWEVER THIS IS BEING SHOWN
 CIRCUITED TO ONE PHASE OF THE ELEVATOR
 MOTOR WHICH IS NOT PERMITTED. PLEASE
 KNOW, THE SD'S IN DWELLING CAN BE
 CIRCUITED TO ONE OF THE ARC FAULT
 PROTECTED BEDRM LIGHTING/RECEPT
 CIRCUITS. THIS WILL ALLEAVIATE THE
 TURNING OFF OF THIS CIRCUIT AND LEAVING
 THE ENTIRE DWELLING WITH OUT SD
 PROTECTION. ( THIS WOULD ALSO ALLEAVIATE
 THE ADDITIONAL AFCI BRKR)
 215.5 NFPA-72 11.8.3
 ** PLEASE SEE 11.8.3 AS STATED ABOVE,
 MISSING SD WHICH IS REQUIRED INSIDE ALL
 SLEEPING ROOMS, WHICH INLCUDE NEW MASTER
 BEDRM. PLEASE KNOW, THE SD SHALL BE
 INSTALLED WITH IN 3' OF THE PEAK ON A
 SLOPED CEILING.
 PLEASE SEE SD'S WILL ALSO BE REQUIRED
 INSIDE AND OUTSIDE OFFICE AS THIS ROOM
 IS CONSIDERED AN ADAPTABLE SLEEPING RM
 7) NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 RANGE AS ONLY 5KW. THIS SEEMS VERY LOW
 FOR A RANGE.
 215.5
  
 8) NOTE:PLEASE SEE LOAD CALCULATIONS
 SHALL INCLUDE ALL LOADS ON EXISTING
 PANEL "C" AS THIS EXISTING PANEL "C" IS
 BEING FED FROM NEW 225A MAIN, YET LOAD
 CALCULATIONS ON SHOW NEW HOUSE PANEL
 LOADS.
 215.5,220.31B. UNABLE TO VERIFY MANY
 ITEMS FROM EXISTING PANEL AND LOADS AT
 THIS TIME. PLEASE SEE NEC FOR MIN LOADS
 REQUIRED FOR DRYER AND WASHER/LAUNDRY.
 220.18, 220.16 ETC.
  
 9) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 10) NOTE: PLEASE SEE MISSING GFI RECEPT
 ALONG KITCHEN COUNTER SPACE PER
 210.52C1,210.8A6.
  
 11) NOTE: PLEASE CLARIFY WATER HEATER,
 NEW , EXISTING ETC. NOWATER HEATER IS
 SHOWN ON ELECTRICAL PLANS. THIS IS SHOWN
 ON "P" SHEETS, HOWEVER THE LOAD SHALL
 ALSO BE INCLUDED WITH LOAD CALCULATIONS
 FOR SERVICE.
 215.5, 220.31B
  
 12) NOTE: PLEASE SEE 408.4 WHERE THE
 PANEL SCHEDULE SHALL BE SPECIFIC FOR
 ROOMS AND ALL AREAS. MOST ARE DONE.
 IE: BEDRM #3 RECEPTS , LIV RM LTS ETC
 ** IT IS KNOWN, THAT DURING CONSTRUCTION
 THESE CIRCUITS MAY CHANGE AND CAN BE
 REVISED AT A LATER DATE.
  
 13) NOTE: PLEASE SEE PLANS INDICATE A
 "SITTING ROOM", HOWEVER THIS SEEMS TO BE
 OUTSIDE SPACE? IF THIS IS A HABITABLE
 ROOM, THEN RECEPT SPACING SHALL MEET
 210.52
  
 14) NOTE: PLEASE SHOW THE LOCATION OF
 THE PANEL "B" ON 2ND FR. NOT LOCATED ON
 PLANS AT THIS TIME. PLEASE BE SURE TO
 SEE 408.7, 240.24D, 110.26 BEFORE
 PLACING PANEL.
  
 15) NOTE: PLEASE CORRELATE FEEDERS TO
 PANEL "B" AS RISER SHOWS ONE SIZE AND
 PANEL SCHEDULE "A" SHOWS ANOTHER.
 215.5, 310.16
  
 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 17) NOTE: PLEASE SEE RISER IS SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 METER TO MAINS. PLEASE SEE THE EQP GRNDS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
 250.6,250.24B
  
 18) NOTE: PLEASE SEE 250.50, 250.32 FOR
 MIN GROUNDING ELECTRODE SYSTEM AT MAIN
 HOUSE. NEW FOOTER STEEL, CWP, GRND ROD
 WILL BE REQUIRED AT MAIN HOUSE. THIS IS
 NOT CONSIDERED AS ONE BUILDING PER FBC
 DEFINITIONS.
  
 19) NOTE: PLEASE SEE GROUNDING ELECTRODE
 RISER AT GUEST HOUSE WHICH INDICATES
 FOOTER STEEL? PLEASE KNOW, AS AN
 EXSITING BUILDING, THIS IS NOT REQUIRED
 AT GUEST HOUSE , ONLY MAIN HOUSE. PLEASE
 KNOW, THE STRUCTURAL INTEGRITY OF THE
 EXISTING FOOTER MAY BE COMPOMISED TO
 ATTACH. PLEASE KNOW, GIVEN THE AGE OF
 THE EXISTING FOOTER IN THIS GUEST HOUSE,
 FOOTER STEEL MAY NOT BE PRESENT AT
 ALL.??
 THIS IS FOR INFORMATION ONLY AS, IT MAY
 BE DONE, BUT NOT REQUIRED AT GUEST
 HOUSE.
  
 20) NOTE: PLEASE SEE DISCONNECT AND AHU
 IN CLOSETS SEEMS TO BE LOCATED
 NOT TO MEET 110.26 AND THE MECHANICAL
 CODE.
 PLEASE ALSO SEE 240.24D AS OCP IS NOT
 PERMITTED IN A CLOTHES/STORAGE CLOSET.
 PLEASE SEE THIS LOCATION AND THE CLOSE
 PROXIMITY TO EASILY IGNITIBLE MATERIALS.
  
 21) NOTE: PLEASE SEE PLANS INDICATE TWO
 EXISTING PANELS AT GUEST HOUSE AND ONLY
 ONE SHOWN ON RISER.?
 PLEASE CORRELATE. 215.5
  
 22) NOTE: PLEASE GO THROUGH ALL SWITCHES
 ON PLANS AS SOME ARE SHOWN, BUT NOT
 GOING TO ANYTHING, OTHERS SHOULD BE
 3-WAY, BUT NOT CLEAR? SEE NOTE ABOVE.
  
 23) NOTE: PLEASE CORRLELATE ALL A/C
 SYSTEMS, OCP AND LOADS, AS THESE SHOWN
 ON ELECTRICAL PANEL SCHEDULE DO NOT
 MATCH WITH THOSE AS SHOWN ON MECH
 SHEETS.
  
 24) NOTE: PLEASE VERIFY THE SIZE OF THE
 NEW METER CAN BEING SHOWN AS 225A?? THIS
 IS NOT KNOWN AS A COMMON SIZE. PLEASE
 ADJUST.
 215.5
  
 ** PLEASE KNOW,MANY OF THE ABOVE ITEMS
 ARE REDLINED ON ONE OF THE SETS OF
 PLANS, HOWEVER IS IN NO WAY ALL
 LOCATIONS AS NOTED ABOVE.
  
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW
 AND IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  