2006-06-25 00:00:00 | ****** UNSAT ******** |
| |
| 1) NOTE: PLEASE BE SURE TO COMPLETELY |
| REMOVED ANY OF THE OLD/VOIDED SHEETS |
| FROM SETS AND ONLY INSERT THE NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| THIS WILL HELP TO AVOID ANY DELAYS IN |
| PROCESSING PROJECT. |
| ** ONE COPY OF ANY OLD/VOIDED REMOVED |
| SHEETS SHOULD BE SUBMITTED SEPARATELY |
| FOR REFERENCE. |
| |
| 2) NOTE: PLEASE SEE CIRCUITING FOR BATH |
| RECEPT ON FIRST FLR IS CIRCUITED TO |
| ELEVATOR LTS. PLEASE SEE |
| 210.52D,210.11C3. BATH(S) REQUIRE |
| DEDICATED CIRCUITS AS SET FORTH IN CODES |
| REF. |
| |
| 3) NOTE: PLEASE SEE PLANS SHALL |
| REFERENCE THE CURRENT CODES IN EFFECT. |
| PLEASE SEE PLANS NOW INDICATE THE |
| "LATEST CODES". WE ARE NOT CURRENTLY |
| UNDER THE LATEST CODES AS THEY HAVE NOT |
| YET BEEN ADOPTED BY THE STATE OF |
| FLORIDA. |
| PLEASE SEE THE FOLLOWING AT A MIN SHOULD |
| BEON PLANS. 2002 NFPA-70, 2003 NFPA-101, |
| 2002 NFPA-72. |
| |
| 4) NOTE: PLEASE SEE THE DISCONNECTING |
| MEANS AT MAIN HOUSE SHOULD BE LOCATED AT |
| THE NEAREST POINT OF ENTRANCE TO THE |
| DWELLING. 225.31-225.34 |
| |
| 5) NOTE: PLEASE SEE MISSING EGRESS |
| LIGHTING CONTROLS IN MANY LOCATIONS. |
| PLEASE SEE ALL RMS IN HOUSE WHICH |
| INDICATE A SW FOR A FAN AND A |
| FAN J-BOX ONLY?? |
| PLEASE KNOW, A LT FIXTURE WILL BE |
| REQUIRED OR 1/2 SWITCHED RECEPT. |
| PLEASE SEE OTHER LOCATIONS IN MAIN HOUSE |
| FOR LOCATIONS OF MEANS OF EGRESS AND |
| WHERE A LT FIXTURE OF SOME SORT WILL BE |
| REQUIRED. |
| PLEASE SEE KITCHEN EGRESS FROM |
| BREAKFAST/PANTRY AREAS? |
| 210.70, LS 101 7.8, RESIDENTIAL CHAPTER |
| 24. |
| |
| 6) NOTE: PLEASE SEE SD'S ARE NOTALL |
| SHOWN WITH CIRCUITING? PLEASE SEE ONE SD |
| IS CIRCUITED HOWEVER THIS IS BEING SHOWN |
| CIRCUITED TO ONE PHASE OF THE ELEVATOR |
| MOTOR WHICH IS NOT PERMITTED. PLEASE |
| KNOW, THE SD'S IN DWELLING CAN BE |
| CIRCUITED TO ONE OF THE ARC FAULT |
| PROTECTED BEDRM LIGHTING/RECEPT |
| CIRCUITS. THIS WILL ALLEAVIATE THE |
| TURNING OFF OF THIS CIRCUIT AND LEAVING |
| THE ENTIRE DWELLING WITH OUT SD |
| PROTECTION. ( THIS WOULD ALSO ALLEAVIATE |
| THE ADDITIONAL AFCI BRKR) |
| 215.5 NFPA-72 11.8.3 |
| ** PLEASE SEE 11.8.3 AS STATED ABOVE, |
| MISSING SD WHICH IS REQUIRED INSIDE ALL |
| SLEEPING ROOMS, WHICH INLCUDE NEW MASTER |
| BEDRM. PLEASE KNOW, THE SD SHALL BE |
| INSTALLED WITH IN 3' OF THE PEAK ON A |
| SLOPED CEILING. |
| PLEASE SEE SD'S WILL ALSO BE REQUIRED |
| INSIDE AND OUTSIDE OFFICE AS THIS ROOM |
| IS CONSIDERED AN ADAPTABLE SLEEPING RM |
| 7) NOTE: PLEASE CLARIFY LOAD SHOWN FOR |
| RANGE AS ONLY 5KW. THIS SEEMS VERY LOW |
| FOR A RANGE. |
| 215.5 |
| |
| 8) NOTE:PLEASE SEE LOAD CALCULATIONS |
| SHALL INCLUDE ALL LOADS ON EXISTING |
| PANEL "C" AS THIS EXISTING PANEL "C" IS |
| BEING FED FROM NEW 225A MAIN, YET LOAD |
| CALCULATIONS ON SHOW NEW HOUSE PANEL |
| LOADS. |
| 215.5,220.31B. UNABLE TO VERIFY MANY |
| ITEMS FROM EXISTING PANEL AND LOADS AT |
| THIS TIME. PLEASE SEE NEC FOR MIN LOADS |
| REQUIRED FOR DRYER AND WASHER/LAUNDRY. |
| 220.18, 220.16 ETC. |
| |
| 9) NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 |
| |
| 10) NOTE: PLEASE SEE MISSING GFI RECEPT |
| ALONG KITCHEN COUNTER SPACE PER |
| 210.52C1,210.8A6. |
| |
| 11) NOTE: PLEASE CLARIFY WATER HEATER, |
| NEW , EXISTING ETC. NOWATER HEATER IS |
| SHOWN ON ELECTRICAL PLANS. THIS IS SHOWN |
| ON "P" SHEETS, HOWEVER THE LOAD SHALL |
| ALSO BE INCLUDED WITH LOAD CALCULATIONS |
| FOR SERVICE. |
| 215.5, 220.31B |
| |
| 12) NOTE: PLEASE SEE 408.4 WHERE THE |
| PANEL SCHEDULE SHALL BE SPECIFIC FOR |
| ROOMS AND ALL AREAS. MOST ARE DONE. |
| IE: BEDRM #3 RECEPTS , LIV RM LTS ETC |
| ** IT IS KNOWN, THAT DURING CONSTRUCTION |
| THESE CIRCUITS MAY CHANGE AND CAN BE |
| REVISED AT A LATER DATE. |
| |
| 13) NOTE: PLEASE SEE PLANS INDICATE A |
| "SITTING ROOM", HOWEVER THIS SEEMS TO BE |
| OUTSIDE SPACE? IF THIS IS A HABITABLE |
| ROOM, THEN RECEPT SPACING SHALL MEET |
| 210.52 |
| |
| 14) NOTE: PLEASE SHOW THE LOCATION OF |
| THE PANEL "B" ON 2ND FR. NOT LOCATED ON |
| PLANS AT THIS TIME. PLEASE BE SURE TO |
| SEE 408.7, 240.24D, 110.26 BEFORE |
| PLACING PANEL. |
| |
| 15) NOTE: PLEASE CORRELATE FEEDERS TO |
| PANEL "B" AS RISER SHOWS ONE SIZE AND |
| PANEL SCHEDULE "A" SHOWS ANOTHER. |
| 215.5, 310.16 |
| |
| 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 17) NOTE: PLEASE SEE RISER IS SHOWING |
| "EQUIPMENT GROUNDING CONDUCTORS" FROM |
| METER TO MAINS. PLEASE SEE THE EQP GRNDS |
| ARE ONLY INSTALLED AFTER THE FIRST MEANS |
| OF DISCONNECT. |
| 250.6,250.24B |
| |
| 18) NOTE: PLEASE SEE 250.50, 250.32 FOR |
| MIN GROUNDING ELECTRODE SYSTEM AT MAIN |
| HOUSE. NEW FOOTER STEEL, CWP, GRND ROD |
| WILL BE REQUIRED AT MAIN HOUSE. THIS IS |
| NOT CONSIDERED AS ONE BUILDING PER FBC |
| DEFINITIONS. |
| |
| 19) NOTE: PLEASE SEE GROUNDING ELECTRODE |
| RISER AT GUEST HOUSE WHICH INDICATES |
| FOOTER STEEL? PLEASE KNOW, AS AN |
| EXSITING BUILDING, THIS IS NOT REQUIRED |
| AT GUEST HOUSE , ONLY MAIN HOUSE. PLEASE |
| KNOW, THE STRUCTURAL INTEGRITY OF THE |
| EXISTING FOOTER MAY BE COMPOMISED TO |
| ATTACH. PLEASE KNOW, GIVEN THE AGE OF |
| THE EXISTING FOOTER IN THIS GUEST HOUSE, |
| FOOTER STEEL MAY NOT BE PRESENT AT |
| ALL.?? |
| THIS IS FOR INFORMATION ONLY AS, IT MAY |
| BE DONE, BUT NOT REQUIRED AT GUEST |
| HOUSE. |
| |
| 20) NOTE: PLEASE SEE DISCONNECT AND AHU |
| IN CLOSETS SEEMS TO BE LOCATED |
| NOT TO MEET 110.26 AND THE MECHANICAL |
| CODE. |
| PLEASE ALSO SEE 240.24D AS OCP IS NOT |
| PERMITTED IN A CLOTHES/STORAGE CLOSET. |
| PLEASE SEE THIS LOCATION AND THE CLOSE |
| PROXIMITY TO EASILY IGNITIBLE MATERIALS. |
| |
| 21) NOTE: PLEASE SEE PLANS INDICATE TWO |
| EXISTING PANELS AT GUEST HOUSE AND ONLY |
| ONE SHOWN ON RISER.? |
| PLEASE CORRELATE. 215.5 |
| |
| 22) NOTE: PLEASE GO THROUGH ALL SWITCHES |
| ON PLANS AS SOME ARE SHOWN, BUT NOT |
| GOING TO ANYTHING, OTHERS SHOULD BE |
| 3-WAY, BUT NOT CLEAR? SEE NOTE ABOVE. |
| |
| 23) NOTE: PLEASE CORRLELATE ALL A/C |
| SYSTEMS, OCP AND LOADS, AS THESE SHOWN |
| ON ELECTRICAL PANEL SCHEDULE DO NOT |
| MATCH WITH THOSE AS SHOWN ON MECH |
| SHEETS. |
| |
| 24) NOTE: PLEASE VERIFY THE SIZE OF THE |
| NEW METER CAN BEING SHOWN AS 225A?? THIS |
| IS NOT KNOWN AS A COMMON SIZE. PLEASE |
| ADJUST. |
| 215.5 |
| |
| ** PLEASE KNOW,MANY OF THE ABOVE ITEMS |
| ARE REDLINED ON ONE OF THE SETS OF |
| PLANS, HOWEVER IS IN NO WAY ALL |
| LOCATIONS AS NOTED ABOVE. |
| |
| |
| ** PLEASE SUBMIT THE ABOVE FOR REVIEW |
| AND IF THERE ARE ANY QUESTIONS OR |
| COMMENTS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |