Plan Review Notes For Permit 06040603 |
Permit Number |
06040603 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-01 00:00:00 | | | | | DENIED | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE ARCHITECT WHOSE TITLE BLOCK | | APPEARS ON THE PLAN MUST MUST SIGN AND | | SEAL PLANS PER 481 FS. | | | | 2} THE REFERENCE TO THE 2004 "CODE" IS | | INCORRECT. THE STATE OF FLORIDA IS | | CURRENTLY UNDER THE 2002 NEC. | | | | 3} THERE IS NO PLAN SHOWN FOR THE A/C | | WIRING MENTIONED IN THE DESCRIPTION OF | | WORK ON THE APPLICATION. PLEASE SHOW ALL | | CIRCUITING AND LOCATION OF THE EQUIPMENT | | BEING INSTALLED, ON THE PLAN. | | | | 4} PROVIDE THE AIC INFORMATION REQUIRED | | PER 110.9 & 10, FOR THE SERVICE | | EQUIPMENT PROPOSED. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|