Plan Review Notes
Plan Review Notes For Permit 06040505
Permit Number 06040505
Review Stop M
Sequence Number 1
Notes
Date Text
2006-04-17 00:00:00*** DENIED ***
 1) PLEASE SUBMIT MANUAL J CALCULATIONS,
 PER 2004 FBC/R M1401.3 .
  
 2) PLEASE SHOW COPPER LINE SIZES ON
 MECH. PLAN.
  
 3) PLEASE SHOW JOB ADDRESS ON MECH.
 PLANS.
  
 4) A 12" RETURN AIR DUCT IS TO SMALL FOR
 A 3.5 TON A/C SYSTEM, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.