2006-04-17 00:00:00PROVISO:
 PLANS INDICATE LOW LEVEL ANNUNCIATION
 AT 25 PPM & HIGH LEVEL AT 100 PPM.PER
 2004 FMC 404.1 INDICATES 25 PPM AS A
 MAXIMUM, THEREFORE THE LOW LEVEL SHOULD
 BE SET AT A LEVEL LOWER THAN 25 PPM AND
 THE HIGH LEVEL SHOULD BE SET AT 25 PPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.