Plan Review Notes
Plan Review Notes For Permit 06040495
Permit Number 06040495
Review Stop B
Sequence Number 2
Notes
Date Text
2006-06-24 00:00:00 
 ***CORRECTIONS****
  
 MYRON JACOBS, BUILDING PLANS EXAMINER
 561-805-6726 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY
  
 _XX__1.A NOTICE OF COMMENCEMENT MUST
 BE FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED, FS713.13.
  
 _XX___2.PROVIDE BUILDING HEIGHT ON
 THE PLAN.DESIGN PRESSURES FOR
 BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND
 MUST BE DONE BY AN ENGINEER. DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED
 SEALED ORIGINALS FAC61G15-23.002.THE
 ENGINEERING SHALL MATCH EACH OTHER. THE
 ONES SUBMITTED DOES NOT. PROVIDE
 MATCHING REPORTS WITH THE ORIGINAL SEAL
 AND SIGNATURE OF THE ENGINEER..
  
 _XX___3.PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 _XX___4.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU MAY SHOW ANCHOR SPACING BY
 CIRCLING IT ON THE APPROPRIATE CHARTS ON
 THE PRODUCT APPROVAL.PLEASE USE INK
 RATHER THAN HIGHLIGHTER.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 _XX___6.ON THE PRODUCT APPROVAL,
 MARK WHICH DETAILS APPLY TO THIS JOB.
 PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.
  
 _XX___8.PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED AND
 PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 4 ABOVE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  