Plan Review Notes
Plan Review Notes For Permit 06040474
Permit Number 06040474
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-12 00:00:00DENIED;
 1.FRONTAL APPROACH REQUIRED FOR BREAK
 SINK. FBC-2004 CHAPTER 11 SECTIONS
 11-4.24.2 HIGHT, .3 KNEE CLEARANCE, .4
 DEPTH, .5 CLEAR FLOOR SPACE .6 EXPOSED
 PIPES, AND .7 FAUCET. SHOW DETAIL ON
 PLANS.
 2.AUTOCLAVE WASTE TO BE INDIRECTLY
 WASTED TO THE BUILDING DRAIN FBC-2004
 PLUMBING SEC. 713.3.
 3.HOT WATER REQUIRED AT DENTAL LAVS.
 SEC. 607.1.
 4.AIR ADMITANCE VALVES MUST COMPLY WITH
 SEC. 917.3.1 ONLY FOUR BRANCH INTERVALS
 FROM THE TOP OF STACK. (HOW MANY FLOORS
 ABOVE OFFICE?)
 5.PLEASE SIZE WATER PIPE PER APPENDIX E.
 (SERVICE SIZE SEAMS TOO SMALL)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695