Plan Review Notes For Permit 06040474 |
Permit Number |
06040474 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-12 00:00:00 | DENIED; | | 1.FRONTAL APPROACH REQUIRED FOR BREAK | | SINK. FBC-2004 CHAPTER 11 SECTIONS | | 11-4.24.2 HIGHT, .3 KNEE CLEARANCE, .4 | | DEPTH, .5 CLEAR FLOOR SPACE .6 EXPOSED | | PIPES, AND .7 FAUCET. SHOW DETAIL ON | | PLANS. | | 2.AUTOCLAVE WASTE TO BE INDIRECTLY | | WASTED TO THE BUILDING DRAIN FBC-2004 | | PLUMBING SEC. 713.3. | | 3.HOT WATER REQUIRED AT DENTAL LAVS. | | SEC. 607.1. | | 4.AIR ADMITANCE VALVES MUST COMPLY WITH | | SEC. 917.3.1 ONLY FOUR BRANCH INTERVALS | | FROM THE TOP OF STACK. (HOW MANY FLOORS | | ABOVE OFFICE?) | | 5.PLEASE SIZE WATER PIPE PER APPENDIX E. | | (SERVICE SIZE SEAMS TOO SMALL) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|