Plan Review Notes
Plan Review Notes For Permit 06040474
Permit Number 06040474
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2006-05-12 00:00:00DENIED;
 1. ADD NOTE, VACUUM AND COMPRESSOR
 PIPING TO BE DONE BY A LICENSED MED-GAS
 CONTRACTOR PERMIT REQUIRED.
 2.SUBMIT MANUFACTURE'S INSTALLATION
 INFORMATION FOR COMPRESSOR AND VACUUM
 PUMP.
 3.VACUUM EXUST TO THE OUTSIDE, NFPA 99C
 2002 ADITION, SEC.5.3.3.6.4.1.
 4.SHOW VENTALATION TO EQUIPMENT ROOM,
 OTHER THAN A/C DROP SEC.5.3.3.3.3.
 5.PVC FITTINGS SHALL BE PRESSURE
 SEC.5.3.10.3.4.
 6. AIR LINES TO BE BRAZED. SEC.
 5.3.10.3.1
 6.CLEANOUTS REQUIRED ON VACUUM PIPING
 PER SEC.5.3.10.10.3.
 MED-GAS PLAN REVIEW BY;