Date |
Text |
2006-05-09 00:00:00 | * UNSAT * | | | | 1) NOTE: PLEASE NOTE ON PLANS FOR "NO | | STORAGE" IN ELECTRICAL ROOM WHICH IS | | BEING SHOWN AS A CLOSET. | | PLEASE SEE 110.26,240.24,408.7 | | | | 2) NOTE: PLEASE PROVIDE SIZE AND LOAD ON | | EXISTING SERVICE.. | | PLEASE SEE 220.35 FOR ALTERNATE METHOD. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|