Plan Review Notes
Plan Review Notes For Permit 06040438
Permit Number 06040438
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-25 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A LOAD CALCULATION FOR
 THE LOAD BEING SERVED BY THE GENERATOR.
 LOAD CANNOT EXCEED GENERATOR OUTPUT, SEE
 702.5, 2002 NEC.
  
 2} SHOW ALL SERVICE EQUIPMENT AND
 GENERATOR ATS AND GENERATOR LOCATIONS ON
 THE SITE PLAN. I SEE THE ATS AND
 GENERATOR, BUT MAINS MUST BE GROUPED,
 270.72, DISCONNECTS MUST BE SERVICE
 RATED, 225.31-39. IT IS UNCLEAR HOW
 COMPLIANCE IS MAINTAINED WITHOUT SEEING
 ALL OTHER PANELS AND DISCONNECTS.
  
 3} SUBMIT A PANEL SCHEDULE FOR THE ATS
 PANEL. 106.3.5.4 FBC.
  
 THIS PERMIT CANNOT BE ISSUED UNTILL A
 RESIDENTIAL GENERATOR PERMIT IS ISSUED.
 THERE WAS ELECTRICAL, GAS, AND
 GENERATOR PERMITS APPLIED FOR LAST YEAR.
 SPEAK TO THE OWNER REGARDING THIS ISSUE.
 THE APPLICATION REQUIREMENTS FOR A
 GENERATOR PERMIT ARE ATTACHED FOR YOUR
 REFERENCE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026